400 psig ABMA pressure band

A 400 psig drum uses the intermediate pressure band for a first-pass solids inventory.

Inputs

lb/hr
psig
ppm
%
°F
psig
%
%
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
Drum solids and heat-recovery balance
Drum solids and heat-recovery balanceBLOWDOWN 4.9 %. CYCLES 21.429 ×. BD FLOW 881.1 lb/hr. FUEL SAVINGS 17.1K USD/yrBLOWDOWN4.9%CYCLES21.429×BD FLOW881.1lb/hrFUEL SAVINGS17.1KUSD/yrBOILER DRUM3,000 ppm targetFEEDWATER140 ppm inLIVE STEAMFLASH + HX73.48% recoveredBLOWDOWNRecovered / gross blowdown heat73.48%0%Annual sensible and latent heat100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Blowdown / steam production
4.9%
Blowdown flow
881.1lb/hr
TDS cycles of concentration
21.429×
Fresh make-up flow
6,281.1lb/hr
Total boiler feedwater
18,881.1lb/hr
Effective feedwater TDS
140ppm
Drum TDS target
3,000ppm
ABMA screening value
3,000ppm
Gross annual blowdown heat
2,245.3MMBtu/yr
Generated flash steam with recovery
195.5lb/hr
Usable flash heat
166,388.02Btu/h
Liquid HX heat
87,449.33Btu/h
Annual heat recovered
1,649.9MMBtu/yr
Annual unrecovered heat
595.3MMBtu/yr
Annual fuel energy avoided
2,012.1MMBtu/yr
Annual fuel savings
17,103USD/yr

Check the original case

The screening target is 3,000 ppm. Use the site limit selector to compare an OEM target.

  • Blowdown / steam production4.9 %
  • TDS cycles of concentration21.429 ×
  • Blowdown flow881.1 lb/hr
  • Annual fuel savings17,103 USD/yr

Formulas and assumptions

Steady drum solids

BD/S = F/(B − F); cycles = B/F

F is the effective feedwater TDS, B is the drum target and S is dry steam production. Conductivity is multiplied by an editable site factor. Zero feed TDS gives zero calculated continuous blowdown and unlimited theoretical cycles.

Water balance and screening bands

Feed = S + BD; make-up = feed − returned condensate

ABMA screening values are 3,500 ppm through 300 psig, 3,000 ppm above 300 through 450 psig, and 2,500 ppm above 450 through 600 psig. Use the verified OEM or site target when it is more restrictive.

Flash and heat exchanger

f = (h_f,boiler − h_f,receiver)/h_fg,receiver; Q_BD = BD·(h_f,boiler − h_makeup)

Usable vapor yields flash latent heat. The exchanger recovers an entered fraction of the remaining liquid sensible heat relative to make-up. Divide recovered heat by boiler efficiency to estimate fuel avoided.

Worked examples

Open a case to edit its inputs.