Continuous blowdown without recovery

A boiler sends continuous blowdown to a site cooling system. Estimate the gross annual heat and make-up water burden.

Inputs

lb/hr
psig
ppm
%
°F
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
Drum solids and heat-recovery balance
Drum solids and heat-recovery balanceBLOWDOWN 8.02 %. CYCLES 13.462 ×. BD FLOW 963 lb/hr. FUEL SAVINGS 0 USD/yrBLOWDOWN8.02%CYCLES13.462×BD FLOW963lb/hrFUEL SAVINGS0USD/yrBOILER DRUM3,500 ppm targetFEEDWATER260 ppm inLIVE STEAMDISCHARGERecovery offBLOWDOWNRecovered / gross blowdown heat0%0%Annual sensible and latent heat100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Blowdown / steam production
8.02%
Blowdown flow
963lb/hr
TDS cycles of concentration
13.462×
Fresh make-up flow
8,163lb/hr
Total boiler feedwater
12,963lb/hr
Effective feedwater TDS
260ppm
Drum TDS target
3,500ppm
ABMA screening value
3,500ppm
Gross annual blowdown heat
2,184.2MMBtu/yr
Generated flash steam with recovery
0lb/hr
Usable flash heat
0Btu/h
Liquid HX heat
0Btu/h
Annual heat recovered
0MMBtu/yr
Annual unrecovered heat
2,184.2MMBtu/yr
Annual fuel energy avoided
0MMBtu/yr
Annual fuel savings
0USD/yr

Check the original case

Fuel savings are zero in this configuration. Turning on recovery shows the scale of the opportunity.

  • Blowdown / steam production8.02 %
  • TDS cycles of concentration13.462 ×
  • Blowdown flow963 lb/hr
  • Annual fuel savings0 USD/yr

Formulas and assumptions

Steady drum solids

BD/S = F/(B − F); cycles = B/F

F is the effective feedwater TDS, B is the drum target and S is dry steam production. Conductivity is multiplied by an editable site factor. Zero feed TDS gives zero calculated continuous blowdown and unlimited theoretical cycles.

Water balance and screening bands

Feed = S + BD; make-up = feed − returned condensate

ABMA screening values are 3,500 ppm through 300 psig, 3,000 ppm above 300 through 450 psig, and 2,500 ppm above 450 through 600 psig. Use the verified OEM or site target when it is more restrictive.

Flash and heat exchanger

f = (h_f,boiler − h_f,receiver)/h_fg,receiver; Q_BD = BD·(h_f,boiler − h_makeup)

Usable vapor yields flash latent heat. The exchanger recovers an entered fraction of the remaining liquid sensible heat relative to make-up. Divide recovered heat by boiler efficiency to estimate fuel avoided.