Electric boiler on a kWh tariff

A packaged electric boiler supplies 600 kg/h at 5 bar g. The electricity tariff is $0.12/kWh.

Inputs

lb/hr
psig
°F
%
%
MMBtu/h
Use the metered rate at the same steam load, on an LHV basis for fuel. Enter 0 to omit.
Currency labels your tariff and savings. Enter local prices.
USD/kWh
Use a net (LHV) fuel price. Electric input uses the price per kWh.
h/yr
Boiler energy balance
Boiler energy balanceEFFICIENCY 98.1 %. BOILER HP 40.6 BHP. FIRING RATE 1.384 MMBtu/h. ANNUAL COST 136.33K USD/yrEFFICIENCY98.1%BOILER HP40.6BHPFIRING RATE1.384MMBtu/hANNUAL COST136.33KUSD/yrELECTRIC BOILERELECTRIC INPUTFEEDWATERLIVE STEAMBLOWDOWNSHELL LOSSUseful heat / input98.1% useful0%1.9% total losses100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Thermal efficiency (LHV for fuel)
98.1%
Boiler horsepower
40.6BHP
Firing or electrical input rate
1.384MMBtu/h
Annual energy cost
136,329USD/yr
Steam-to-fuel ratio
3.26lb/kWh
Fuel or electricity rate
405.74kWh/h
Useful steam duty
1.358MMBtu/h
Stack loss
0%
Direct input/output efficiency
—
Approx. excess air from dry O₂
—
Shell and radiation loss
0.7%
Blowdown loss
1.2%
Feedwater enthalpy
158.23Btu/lb
Delivered steam enthalpy
1,184.97Btu/lb

Check the original case

Stack loss is zero. Read the electrical input in kWh per hour and the steam yield per kWh.

  • Thermal efficiency (LHV for fuel)98.1 %
  • Boiler horsepower40.6 BHP
  • Firing or electrical input rate1.384 MMBtu/h
  • Annual energy cost136,329 USD/yr

Formulas and assumptions

Useful duty and rating

Q_steam = m_steam·(h_g − h_feed); 1 BHP = 33,475 Btu/h

Steam is dry saturated and feedwater enthalpy is evaluated at boiler pressure.

Direct efficiency and excess air

η_direct = 100·Q_steam/Q_measured; EA ≈ 100·O₂/(21 − O₂)

Meter steam and energy input at the same operating condition on a consistent heat basis. The dry oxygen ratio is a screening approximation for complete combustion. Use the ASME test boundary and measured flows and losses for a formal acceptance test.

Indirect efficiency

η = 100 − ΔT·[A₂/(21 − O₂) + B] − L_shell − L_bd

Use a Celsius temperature difference and dry oxygen in percent. Testo coefficients (A₂, B) are (0.65, 0.009) for natural gas, (0.68, 0.007) for either oil and (0.63, 0.008) for propane. The wood screen uses 0.74·ΔT/CO₂ with estimated CO₂ = 20·(21 − O₂)/21. Electric stack loss is zero.

Fuel and annual cost

Q_input = Q_steam/(η/100); m_fuel = Q_input/LHV; cost = Q_input·hours·tariff

Illustrative LHVs in MJ/kg are 48.2 gas, 42.8 No. 2 oil, 39.5 No. 6 oil, 46.3 propane and 16 wood. Electric input is priced in kWh. Boiler loads and tariffs are held constant over the entered hours.