No. 6 oil process boiler

A residual-oil boiler supplies 22,000 lb/hr from a high-pressure process drum. It operates for 7,400 hours each year.

Inputs

lb/hr
psig
°F
°F
°F
%
%
%
MMBtu/h
Use the metered rate at the same steam load, on an LHV basis for fuel. Enter 0 to omit.
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
Use a net (LHV) fuel price. Electric input uses the price per kWh.
h/yr
Boiler energy balance
Boiler energy balanceEFFICIENCY 86.24 %. BOILER HP 683.5 BHP. FIRING RATE 26.529 MMBtu/h. ANNUAL COST 2.94M USD/yrEFFICIENCY86.24%BOILER HP683.5BHPFIRING RATE26.529MMBtu/hANNUAL COST2.94MUSD/yrSTEAM DRUMFUEL + AIRFEEDWATERLIVE STEAMBLOWDOWNSTACK 11.26%SHELL LOSSUseful heat / input86.24% useful0%13.76% total losses100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Thermal efficiency (LHV for fuel)
86.24%
Boiler horsepower
683.5BHP
Firing or electrical input rate
26.529MMBtu/h
Annual energy cost
2,944,715USD/yr
Steam-to-fuel ratio
14.08lb/lb fuel
Fuel or electricity rate
1,562.2lb/hr
Useful steam duty
22.879MMBtu/h
Stack loss
11.26%
Direct input/output efficiency
—
Approx. excess air from dry O₂
32.91%
Shell and radiation loss
1.5%
Blowdown loss
1%
Feedwater enthalpy
158.48Btu/lb
Delivered steam enthalpy
1,198.43Btu/lb

Check the original case

Switch to No. 2 oil at the same conditions to isolate the effect of the assumed heating value on fuel mass.

  • Thermal efficiency (LHV for fuel)86.24 %
  • Boiler horsepower683.5 BHP
  • Firing or electrical input rate26.529 MMBtu/h
  • Annual energy cost2,944,715 USD/yr

Formulas and assumptions

Useful duty and rating

Q_steam = m_steam·(h_g − h_feed); 1 BHP = 33,475 Btu/h

Steam is dry saturated and feedwater enthalpy is evaluated at boiler pressure.

Direct efficiency and excess air

η_direct = 100·Q_steam/Q_measured; EA ≈ 100·O₂/(21 − O₂)

Meter steam and energy input at the same operating condition on a consistent heat basis. The dry oxygen ratio is a screening approximation for complete combustion. Use the ASME test boundary and measured flows and losses for a formal acceptance test.

Indirect efficiency

η = 100 − ΔT·[A₂/(21 − O₂) + B] − L_shell − L_bd

Use a Celsius temperature difference and dry oxygen in percent. Testo coefficients (A₂, B) are (0.65, 0.009) for natural gas, (0.68, 0.007) for either oil and (0.63, 0.008) for propane. The wood screen uses 0.74·ΔT/CO₂ with estimated CO₂ = 20·(21 − O₂)/21. Electric stack loss is zero.

Fuel and annual cost

Q_input = Q_steam/(η/100); m_fuel = Q_input/LHV; cost = Q_input·hours·tariff

Illustrative LHVs in MJ/kg are 48.2 gas, 42.8 No. 2 oil, 39.5 No. 6 oil, 46.3 propane and 16 wood. Electric input is priced in kWh. Boiler loads and tariffs are held constant over the entered hours.

Worked examples