Propane boiler at a remote plant
A remote plant uses propane to supply a 60 psig steam header. Use its net energy tariff to estimate the annual bill.
Inputs
Inputs
- Steam production
- 4,500 lb/hr
- Boiler pressure
- 60 psig
- Feedwater temperature
- 190 °F
- Fuel or electricity
- Propane
- Stack temperature
- 356 °F
- Combustion air temperature
- 68 °F
- Dry stack oxygen O₂
- 4 %
- Shell and radiation loss
- 1.5 %
- Blowdown loss allowance
- 1 %
- Measured energy input (optional)
- 0 MMBtu/h
- Currency
- USD
- Energy price
- 25 USD/MMBtu
- Annual operating time
- 3,500 h/yr
Calculation results
- Thermal efficiency (LHV for fuel)
- 90.29%
- Boiler horsepower
- 137.6BHP
- Firing or electrical input rate
- 5.103MMBtu/h
- Annual energy cost
- 446,488USD/yr
- Steam-to-fuel ratio
- 17.55lb/lb fuel
- Fuel or electricity rate
- 256.3lb/hr
- Useful steam duty
- 4.607MMBtu/h
- Stack loss
- 7.21%
- Direct input/output efficiency
- —
- Approx. excess air from dry O₂
- 23.53%
- Shell and radiation loss
- 1.5%
- Blowdown loss
- 1%
- Feedwater enthalpy
- 158.2Btu/lb
- Delivered steam enthalpy
- 1,182.04Btu/lb
Calculation basis
- Useful duty and rating
Q_steam = m_steam·(h_g − h_feed); 1 BHP = 33,475 Btu/h - Direct efficiency and excess air
η_direct = 100·Q_steam/Q_measured; EA ≈ 100·O₂/(21 − O₂) - Indirect efficiency
η = 100 − ΔT·[A₂/(21 − O₂) + B] − L_shell − L_bd - Fuel and annual cost
Q_input = Q_steam/(η/100); m_fuel = Q_input/LHV; cost = Q_input·hours·tariff
Check the original case
The propane coefficients affect stack loss and the LHV determines the steam-to-fuel mass ratio.
- Thermal efficiency (LHV for fuel)90.29 %
- Boiler horsepower137.6 BHP
- Firing or electrical input rate5.103 MMBtu/h
- Annual energy cost446,488 USD/yr
Formulas and assumptions
Useful duty and rating
Q_steam = m_steam·(h_g − h_feed); 1 BHP = 33,475 Btu/h
Steam is dry saturated and feedwater enthalpy is evaluated at boiler pressure.
Direct efficiency and excess air
η_direct = 100·Q_steam/Q_measured; EA ≈ 100·O₂/(21 − O₂)
Meter steam and energy input at the same operating condition on a consistent heat basis. The dry oxygen ratio is a screening approximation for complete combustion. Use the ASME test boundary and measured flows and losses for a formal acceptance test.
Indirect efficiency
η = 100 − ΔT·[A₂/(21 − O₂) + B] − L_shell − L_bd
Use a Celsius temperature difference and dry oxygen in percent. Testo coefficients (A₂, B) are (0.65, 0.009) for natural gas, (0.68, 0.007) for either oil and (0.63, 0.008) for propane. The wood screen uses 0.74·ΔT/CO₂ with estimated CO₂ = 20·(21 − O₂)/21. Electric stack loss is zero.
Fuel and annual cost
Q_input = Q_steam/(η/100); m_fuel = Q_input/LHV; cost = Q_input·hours·tariff
Illustrative LHVs in MJ/kg are 48.2 gas, 42.8 No. 2 oil, 39.5 No. 6 oil, 46.3 propane and 16 wood. Electric input is priced in kWh. Boiler loads and tariffs are held constant over the entered hours.
Worked examples
Open a case to edit its inputs.