Wood biomass steam boiler

A wood-fired process boiler delivers 8,000 kg/h. Model dry stack oxygen and use an illustrative as-fired fuel heating value.

Inputs

lb/hr
psig
°F
°F
°F
%
%
%
MMBtu/h
Use the metered rate at the same steam load, on an LHV basis for fuel. Enter 0 to omit.
Currency labels your tariff and savings. Enter local prices.
EUR/MMBtu
Use a net (LHV) fuel price. Electric input uses the price per kWh.
h/yr
Boiler energy balance
Boiler energy balanceEFFICIENCY 85.24 %. BOILER HP 546.4 BHP. FIRING RATE 21.458 MMBtu/h. ANNUAL COST 950.86K EUR/yrEFFICIENCY85.24%BOILER HP546.4BHPFIRING RATE21.458MMBtu/hANNUAL COST950.86KEUR/yrSTEAM DRUMFUEL + AIRFEEDWATERLIVE STEAMBLOWDOWNSTACK 10.76%SHELL LOSSUseful heat / input85.24% useful0%14.76% total losses100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

  • Wood-fuel screen uses estimated dry CO₂ and an assumed 16 MJ/kg as-fired LHV.
Thermal efficiency (LHV for fuel)
85.24%
Boiler horsepower
546.4BHP
Firing or electrical input rate
21.458MMBtu/h
Annual energy cost
950,859EUR/yr
Steam-to-fuel ratio
5.65lb/lb fuel
Fuel or electricity rate
3,119.5lb/hr
Useful steam duty
18.291MMBtu/h
Stack loss
10.76%
Direct input/output efficiency
—
Approx. excess air from dry O₂
61.54%
Shell and radiation loss
3%
Blowdown loss
1%
Feedwater enthalpy
158.4Btu/lb
Delivered steam enthalpy
1,195.49Btu/lb

Check the original case

Check the wood-fuel screening note and compare the result against a measured fuel analysis when available.

  • Thermal efficiency (LHV for fuel)85.24 %
  • Boiler horsepower546.4 BHP
  • Firing or electrical input rate21.458 MMBtu/h
  • Annual energy cost950,859 EUR/yr

Formulas and assumptions

Useful duty and rating

Q_steam = m_steam·(h_g − h_feed); 1 BHP = 33,475 Btu/h

Steam is dry saturated and feedwater enthalpy is evaluated at boiler pressure.

Direct efficiency and excess air

η_direct = 100·Q_steam/Q_measured; EA ≈ 100·O₂/(21 − O₂)

Meter steam and energy input at the same operating condition on a consistent heat basis. The dry oxygen ratio is a screening approximation for complete combustion. Use the ASME test boundary and measured flows and losses for a formal acceptance test.

Indirect efficiency

η = 100 − ΔT·[A₂/(21 − O₂) + B] − L_shell − L_bd

Use a Celsius temperature difference and dry oxygen in percent. Testo coefficients (A₂, B) are (0.65, 0.009) for natural gas, (0.68, 0.007) for either oil and (0.63, 0.008) for propane. The wood screen uses 0.74·ΔT/CO₂ with estimated CO₂ = 20·(21 − O₂)/21. Electric stack loss is zero.

Fuel and annual cost

Q_input = Q_steam/(η/100); m_fuel = Q_input/LHV; cost = Q_input·hours·tariff

Illustrative LHVs in MJ/kg are 48.2 gas, 42.8 No. 2 oil, 39.5 No. 6 oil, 46.3 propane and 16 wood. Electric input is priced in kWh. Boiler loads and tariffs are held constant over the entered hours.

Worked examples