Engineering methodology
The calculators use steady-state mass and energy balances with industrial steam properties. Each calculator lists its governing equations and the input assumptions that affect its result.
Steam properties and verification
Gauge inputs use a fixed 1.01325 bar atmosphere. The property engine evaluates IAPWS-IF97 Regions 1, 2 and 4 over 0–600 psig. Superheated states use Region 2 up to 600 °C. Wet mixtures use mass-weighted liquid and vapor properties.
The verification suite checks the equation release’s verification points, ASME saturation table rows and independently tabulated NIST IAPWS-95 states. The ASME check tolerances are 0.002 °C for saturation, 0.11 kJ/kg for enthalpy and 0.01% for saturated vapor volume. The independent NIST saturation check tolerances are 0.02 °C, 0.35 kJ/kg and 0.15% volume. These are reference-point comparisons.
Units, hours and tariffs
State is stored at full precision in metric units. The display converts pressure, temperatures, mass, energy and tariffs without reusing rounded screen values. Currency codes label costs. For a fuel estimate, put the tariff, emission factor and boiler efficiency on the same heating-value basis. The Siegert boiler model uses LHV and the trap default emission factor uses HHV.
Model references
- Steam propertiesFind saturation temperature, enthalpy, entropy, volume and density for dry saturated, wet or superheated steam from gauge pressure.
- Boiler efficiencyEstimate steam-to-fuel ratio, boiler horsepower, firing rate and annual fuel cost from steam output and measured stack losses.
- Boiler blowdownBalance boiler solids to estimate cycles, continuous blowdown, make-up demand and flash/HX heat-recovery savings.
- Flash steam recoveryCalculate flash fraction across a pressure drop, usable flash steam, return heat credit and annual fuel and treatment savings.
- Steam header sizingScreen Schedule 40 or 80 steam headers for velocity, Darcy pressure drop and bare versus insulated heat loss.
- Heat exchanger dutyCalculate continuous or batch heating duty, condensing steam rate, trap capacity and saturated-steam control-valve Cv.
- Steam trap leak costEstimate failed-open trap leakage with the Napier orifice equation, annual fuel, cost and direct CO₂ emissions.
- Deaerator pegging steamBalance make-up, hot condensate, pegging steam and saturated vent losses to find deaerator outlet and net firing relief.