1/8 in trap on a 15 psig header

Two small failed-open traps discharge from a low-pressure header to atmosphere.

Inputs

in
1/8–1/2 in, equivalent to 3.175–12.7 mm.
psig
psig
h/yr
°F
%
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
kg CO₂/MMBtu
Default is EPA natural gas on an HHV basis. Match efficiency, tariff and factor to the same fuel basis.
Failed orifice and annual loss by diameter
Failed orifice and annual loss by diameterLEAK / TRAP 6.7 lb/hr. TOTAL LEAK 13.5 lb/hr. ANNUAL COST 485 USD/yr. CO₂ / YEAR 3.34 US ton/yrLEAK / TRAP6.7lb/hrTOTAL LEAK13.5lb/hrANNUAL COST485USD/yrCO₂ / YEAR3.34US ton/yrOPEN ORIFICE0.125 inANNUAL LOSS · USD1/8 in4851/4 in1,9413/8 in4,3661/2 in7,762Effective orifice diameterChoked discharge1/8 inOpening size1/2 in
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Live steam per trap
6.7lb/hr
Total live steam leak
13.5lb/hr
Annual steam mass lost
22.94US ton/yr
Annual useful energy lost
46.8MMBtu/yr
Annual fuel energy wasted
57.1MMBtu/yr
Annual fuel cost
485USD/yr
Annual direct CO₂
3.34US ton/yr
Discharge flow regime
Choked
Discharge / upstream absolute P
49.49%
Boiler enthalpy rise
1,019.88Btu/lb

Check the original case

The model uses absolute pressure in the flow equation. Changing discharge pressure can move the case out of choked flow.

  • Live steam per trap6.7 lb/hr
  • Total live steam leak13.5 lb/hr
  • Annual fuel cost485 USD/yr
  • Annual direct CO₂3.34 US ton/yr

Formulas and assumptions

Napier sharp-orifice screen

m = 24.24·C_d·d²·P_abs·N

The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.

Fuel and cost

Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff

The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.

Direct CO₂

CO₂ = annual fuel energy·fuel emission factor

The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.

Worked examples

Open a case to edit its inputs.