1/8 in trap on a 15 psig header
Two small failed-open traps discharge from a low-pressure header to atmosphere.
Inputs
Inputs
- Effective orifice diameter
- 0.125 in
- Steam header pressure
- 15 psig
- Discharge pressure
- 0 psig
- Failed-open trap count
- 2
- Discharge coefficient C_d
- 0.6
- Annual operating time
- 3,400 h/yr
- Boiler feedwater temperature
- 176 °F
- Boiler efficiency
- 82 %
- Currency
- USD
- Energy price
- 8.5 USD/MMBtu
- Fuel CO₂ factor
- 53.06 kg CO₂/MMBtu
Calculation results
- Live steam per trap
- 6.7lb/hr
- Total live steam leak
- 13.5lb/hr
- Annual steam mass lost
- 22.94US ton/yr
- Annual useful energy lost
- 46.8MMBtu/yr
- Annual fuel energy wasted
- 57.1MMBtu/yr
- Annual fuel cost
- 485USD/yr
- Annual direct CO₂
- 3.34US ton/yr
- Discharge flow regime
- Choked
- Discharge / upstream absolute P
- 49.49%
- Boiler enthalpy rise
- 1,019.88Btu/lb
Calculation basis
- Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N - Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff - Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
Check the original case
The model uses absolute pressure in the flow equation. Changing discharge pressure can move the case out of choked flow.
- Live steam per trap6.7 lb/hr
- Total live steam leak13.5 lb/hr
- Annual fuel cost485 USD/yr
- Annual direct CO₂3.34 US ton/yr
Formulas and assumptions
Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N
The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.
Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff
The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.
Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.
Worked examples
Open a case to edit its inputs.