Oil-fired steam leak and CO₂ cost basis
An oil-fired plant uses the EPA No. 2 oil direct CO₂ factor of 73.96 kg/MMBtu HHV.
Inputs
Inputs
- Effective orifice diameter
- 0.25 in
- Steam header pressure
- 180 psig
- Discharge pressure
- 0 psig
- Failed-open trap count
- 6
- Discharge coefficient C_d
- 0.65
- Annual operating time
- 6,700 h/yr
- Boiler feedwater temperature
- 176 °F
- Boiler efficiency
- 81 %
- Currency
- USD
- Energy price
- 20 USD/MMBtu
- Fuel CO₂ factor
- 73.96 kg CO₂/MMBtu
Calculation results
- Live steam per trap
- 191.7lb/hr
- Total live steam leak
- 1,150.4lb/hr
- Annual steam mass lost
- 3,853.71US ton/yr
- Annual useful energy lost
- 8,123.5MMBtu/yr
- Annual fuel energy wasted
- 10,029MMBtu/yr
- Annual fuel cost
- 200,580USD/yr
- Annual direct CO₂
- 817.63US ton/yr
- Discharge flow regime
- Choked
- Discharge / upstream absolute P
- 7.55%
- Boiler enthalpy rise
- 1,053.98Btu/lb
Calculation basis
- Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N - Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff - Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
Check the original case
Use the site fuel cost, heating-value basis and direct emission factor to compare repair payback.
- Live steam per trap191.7 lb/hr
- Total live steam leak1,150.4 lb/hr
- Annual fuel cost200,580 USD/yr
- Annual direct CO₂817.63 US ton/yr
Formulas and assumptions
Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N
The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.
Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff
The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.
Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.
Worked examples
Open a case to edit its inputs.