Oil-fired steam leak and CO₂ cost basis

An oil-fired plant uses the EPA No. 2 oil direct CO₂ factor of 73.96 kg/MMBtu HHV.

Inputs

in
1/8–1/2 in, equivalent to 3.175–12.7 mm.
psig
psig
h/yr
°F
%
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
kg CO₂/MMBtu
Default is EPA natural gas on an HHV basis. Match efficiency, tariff and factor to the same fuel basis.
Failed orifice and annual loss by diameter
Failed orifice and annual loss by diameterLEAK / TRAP 191.7 lb/hr. TOTAL LEAK 1,150.4 lb/hr. ANNUAL COST 200.58K USD/yr. CO₂ / YEAR 817.63 US ton/yrLEAK / TRAP191.7lb/hrTOTAL LEAK1,150.4lb/hrANNUAL COST200.58KUSD/yrCO₂ / YEAR817.63US ton/yrOPEN ORIFICE0.25 inANNUAL LOSS · USD1/8 in50.15K1/4 in200.58K3/8 in451.31K1/2 in802.32KEffective orifice diameterChoked discharge1/8 inOpening size1/2 in
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Live steam per trap
191.7lb/hr
Total live steam leak
1,150.4lb/hr
Annual steam mass lost
3,853.71US ton/yr
Annual useful energy lost
8,123.5MMBtu/yr
Annual fuel energy wasted
10,029MMBtu/yr
Annual fuel cost
200,580USD/yr
Annual direct CO₂
817.63US ton/yr
Discharge flow regime
Choked
Discharge / upstream absolute P
7.55%
Boiler enthalpy rise
1,053.98Btu/lb

Check the original case

Use the site fuel cost, heating-value basis and direct emission factor to compare repair payback.

  • Live steam per trap191.7 lb/hr
  • Total live steam leak1,150.4 lb/hr
  • Annual fuel cost200,580 USD/yr
  • Annual direct CO₂817.63 US ton/yr

Formulas and assumptions

Napier sharp-orifice screen

m = 24.24·C_d·d²·P_abs·N

The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.

Fuel and cost

Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff

The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.

Direct CO₂

CO₂ = annual fuel energy·fuel emission factor

The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.

Worked examples

Open a case to edit its inputs.