1/2 in opening on a 250 psig header
A large failed-open trap leaks from a high-pressure main for most of the year.
Inputs
Inputs
- Effective orifice diameter
- 0.5 in
- Steam header pressure
- 250 psig
- Discharge pressure
- 0 psig
- Failed-open trap count
- 1
- Discharge coefficient C_d
- 0.7
- Annual operating time
- 7,800 h/yr
- Boiler feedwater temperature
- 176 °F
- Boiler efficiency
- 82 %
- Currency
- USD
- Energy price
- 12 USD/MMBtu
- Fuel CO₂ factor
- 53.06 kg CO₂/MMBtu
Calculation results
- Live steam per trap
- 1,122.8lb/hr
- Total live steam leak
- 1,122.8lb/hr
- Annual steam mass lost
- 4,379.08US ton/yr
- Annual useful energy lost
- 9,262.5MMBtu/yr
- Annual fuel energy wasted
- 11,295.8MMBtu/yr
- Annual fuel cost
- 135,549USD/yr
- Annual direct CO₂
- 660.68US ton/yr
- Discharge flow regime
- Choked
- Discharge / upstream absolute P
- 5.55%
- Boiler enthalpy rise
- 1,057.59Btu/lb
Calculation basis
- Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N - Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff - Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
Check the original case
Compare the diameter chart with the quarter-inch case. At fixed pressures, loss scales with the square of diameter.
- Live steam per trap1,122.8 lb/hr
- Total live steam leak1,122.8 lb/hr
- Annual fuel cost135,549 USD/yr
- Annual direct CO₂660.68 US ton/yr
Formulas and assumptions
Napier sharp-orifice screen
m = 24.24·C_d·d²·P_abs·N
The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.
Fuel and cost
Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff
The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.
Direct CO₂
CO₂ = annual fuel energy·fuel emission factor
The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.
Worked examples
Open a case to edit its inputs.