DOE Napier 130 psig reference

The DOE pressure reduction brief evaluates a sharp-edged 1/4 in orifice at 130 psig as a theoretical loss.

Inputs

in
1/8–1/2 in, equivalent to 3.175–12.7 mm.
psig
psig
h/yr
°F
%
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
kg CO₂/MMBtu
Default is EPA natural gas on an HHV basis. Match efficiency, tariff and factor to the same fuel basis.
Failed orifice and annual loss by diameter
Failed orifice and annual loss by diameterLEAK / TRAP 219.2 lb/hr. TOTAL LEAK 219.2 lb/hr. ANNUAL COST 15.5K USD/yr. CO₂ / YEAR 106.67 US ton/yrLEAK / TRAP219.2lb/hrTOTAL LEAK219.2lb/hrANNUAL COST15.5KUSD/yrCO₂ / YEAR106.67US ton/yrOPEN ORIFICE0.25 inANNUAL LOSS · USD1/8 in3,8761/4 in15.5K3/8 in34.88K1/2 in62.01KEffective orifice diameterChoked discharge1/8 inOpening size1/2 in
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Live steam per trap
219.2lb/hr
Total live steam leak
219.2lb/hr
Annual steam mass lost
712.45US ton/yr
Annual useful energy lost
1,495.5MMBtu/yr
Annual fuel energy wasted
1,823.8MMBtu/yr
Annual fuel cost
15,503USD/yr
Annual direct CO₂
106.67US ton/yr
Discharge flow regime
Choked
Discharge / upstream absolute P
10.16%
Boiler enthalpy rise
1,049.58Btu/lb

Check the original case

Recomputing the DOE brief’s printed equation at 144.696 psia gives about 219.2 lb/hr. The brief’s worked line prints 210.5 lb/hr.

  • Live steam per trap219.2 lb/hr
  • Total live steam leak219.2 lb/hr
  • Annual fuel cost15,503 USD/yr
  • Annual direct CO₂106.67 US ton/yr

Formulas and assumptions

Napier sharp-orifice screen

m = 24.24·C_d·d²·P_abs·N

The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.

Fuel and cost

Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff

The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.

Direct CO₂

CO₂ = annual fuel energy·fuel emission factor

The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.

Worked examples

Open a case to edit its inputs.