Trap discharging to high backpressure

A return system imposes 35 psig backpressure on traps fed by a 50 psig header.

Inputs

in
1/8–1/2 in, equivalent to 3.175–12.7 mm.
psig
psig
h/yr
°F
%
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
kg CO₂/MMBtu
Default is EPA natural gas on an HHV basis. Match efficiency, tariff and factor to the same fuel basis.
Failed orifice and annual loss by diameter
Failed orifice and annual loss by diameterLEAK / TRAP 33.8 lb/hr. TOTAL LEAK 101.3 lb/hr. ANNUAL COST 4,567 USD/yr. CO₂ / YEAR 31.43 US ton/yrLEAK / TRAP33.8lb/hrTOTAL LEAK101.3lb/hrANNUAL COST4,567USD/yrCO₂ / YEAR31.43US ton/yrOPEN ORIFICE0.1875 inANNUAL LOSS · USD1/8 in2,0301/4 in8,1193/8 in18.27K1/2 in32.48KEffective orifice diameterSubcritical discharge1/8 inOpening size1/2 in
Live steam / heatCondensate / waterDischarge / loss

Calculation results

  • Unchoked pressure ratio. A normalized isentropic correction is applied to the Napier screen.
Live steam per trap
33.8lb/hr
Total live steam leak
101.3lb/hr
Annual steam mass lost
212.81US ton/yr
Annual useful energy lost
440.6MMBtu/yr
Annual fuel energy wasted
537.3MMBtu/yr
Annual fuel cost
4,567USD/yr
Annual direct CO₂
31.43US ton/yr
Discharge flow regime
Subcritical
Discharge / upstream absolute P
76.81%
Boiler enthalpy rise
1,035.14Btu/lb

Check the original case

Read the subcritical regime and compare the leak against the same traps vented to atmosphere.

  • Live steam per trap33.8 lb/hr
  • Total live steam leak101.3 lb/hr
  • Annual fuel cost4,567 USD/yr
  • Annual direct CO₂31.43 US ton/yr

Formulas and assumptions

Napier sharp-orifice screen

m = 24.24·C_d·d²·P_abs·N

The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.

Fuel and cost

Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff

The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.

Direct CO₂

CO₂ = annual fuel energy·fuel emission factor

The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.