Four 1/4 in leaking traps

Four traps have effective 1/4 in openings on a 125 psig header and discharge to atmosphere.

Inputs

in
1/8–1/2 in, equivalent to 3.175–12.7 mm.
psig
psig
h/yr
°F
%
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
kg CO₂/MMBtu
Default is EPA natural gas on an HHV basis. Match efficiency, tariff and factor to the same fuel basis.
Failed orifice and annual loss by diameter
Failed orifice and annual loss by diameterLEAK / TRAP 148.1 lb/hr. TOTAL LEAK 592.6 lb/hr. ANNUAL COST 41.88K USD/yr. CO₂ / YEAR 288.21 US ton/yrLEAK / TRAP148.1lb/hrTOTAL LEAK592.6lb/hrANNUAL COST41.88KUSD/yrCO₂ / YEAR288.21US ton/yrOPEN ORIFICE0.25 inANNUAL LOSS · USD1/8 in10.47K1/4 in41.88K3/8 in94.24K1/2 in167.54KEffective orifice diameterChoked discharge1/8 inOpening size1/2 in
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Live steam per trap
148.1lb/hr
Total live steam leak
592.6lb/hr
Annual steam mass lost
1,925.92US ton/yr
Annual useful energy lost
4,040.6MMBtu/yr
Annual fuel energy wasted
4,927.6MMBtu/yr
Annual fuel cost
41,885USD/yr
Annual direct CO₂
288.21US ton/yr
Discharge flow regime
Choked
Discharge / upstream absolute P
10.52%
Boiler enthalpy rise
1,049.01Btu/lb

Check the original case

Compare the per-trap and total loss. The annual cost scales with the number of confirmed failed-open traps.

  • Live steam per trap148.1 lb/hr
  • Total live steam leak592.6 lb/hr
  • Annual fuel cost41,885 USD/yr
  • Annual direct CO₂288.21 US ton/yr

Formulas and assumptions

Napier sharp-orifice screen

m = 24.24·C_d·d²·P_abs·N

The US formula gives lb/h for effective diameter in inches, upstream pressure in psia and N failed traps. It applies to dry steam in choked discharge. For higher pressure ratios, a normalized isentropic correction with k = 1.30 trends to zero at equal pressure.

Fuel and cost

Fuel = m·(h_g − h_feed)·hours/η; cost = fuel·tariff

The display uses the difference between dry vapor and boiler feedwater rather than a fixed steam value. An actual trap may have a different seat geometry and effective opening.

Direct CO₂

CO₂ = annual fuel energy·fuel emission factor

The EPA natural-gas default is 53.06 kg CO₂/MMBtu HHV. Enter the correct factor and aligned efficiency and energy tariff for other fuels.

Worked examples

Open a case to edit its inputs.