Use a pedestal large enough to exceed the confinement cap. The bearing factor remains at two as the supporting area increases.
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
ANSI/AISC 360-22J8 · DG 1
Inputs
LRFD
Use loads and strengths from the selected method. Re-enter values after switching methods.
Base plate plan
Within modeled limits
Bearing P
1,237.6kip
Bearing area
60.633in²
Min. plate t
0.912in
Gov. length
3in
The dashed rectangle is the 0.95d × 0.80b_f effective column footprint used to measure m and n.
Calculation results
Limit state
Demand
Available
Use
Concrete bearing
335 kip
1,237.6 kip
27.1%
Plate thickness
0.912 in
1 in
91.2%
Calculation values
Plate area A₁
224 in²
Similar support area A₂
1,263.5 in²
Confinement multiplier
2
Applied bearing pressure
1.496 ksi
Projection m
2.775 in
Projection n
3 in
Inner projection n′
2.622 in
Yield-line factor λ
0.56
Effective inner λn′
1.47 in
Nominal concrete bearing
1,904 kip
Available bearing · LRFD
1,237.6 kip
Available bearing · ASD
824.242 kip
SteelBeamLab / AISC 360-22 J8 · DG 1
Base plate with capped confinement
LRFD · US customary
For an I-shaped column in centered full-contact compression on a rectangular pedestal. Check the governing concrete code, anchors, grout, welds, and any eccentric load separately.
Entered values
Required compression Pᵣ
335 kip
Column depth d
11 in
Column flange width b_f
10 in
Plate length N
16 in
Plate width B
14 in
Trial thickness t
1 in
Steel yield stress Fᵧ
36 ksi
Pedestal length
38 in
Pedestal width
35 in
Concrete strength f′c
5 ksi
Key results
Bearing P
1,237.6kip
Bearing area
60.633in²
Min. plate t
0.912in
Gov. length
3in
Limit-state screening
Limit state
Demand
Available
Use
Concrete bearing
335 kip
1,237.6 kip
27.1%
Plate thickness
0.912 in
1 in
91.2%
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
Worked solution at the starting values
Use bearing area 224 in² and confinement multiplier 2.
Compare m = 2.775 in, n = 3 in, and λn′ = 1.47 in.
Use the governing projection to calculate the minimum plate thickness of 0.912 in.
Calculation basis
For an I-shaped column in centered full-contact compression on a rectangular pedestal. Check the governing concrete code, anchors, grout, welds, and any eccentric load separately.
Concrete confinement
J8 uses 0.85f′cA₁ times the lesser of 2 and √(A₂/A₁). Here A₂ is the largest centered rectangle similar to the plate that fits on the pedestal. Use φc = 0.65 or Ωc = 2.31. The required bearing-only area holds the plate aspect ratio and pedestal fixed.
Plate projection
DG 1 uses m = (N − 0.95d)/2, n = (B − 0.80b_f)/2, and n′ = √(db_f)/4. With X = [4db_f/(d + b_f)²](Pᵣ/available concrete bearing), λ = 2√X/(1 + √(1 − X)), capped at one. The governing projection is the largest of m, n, and λn′.
Thickness
Use tₘᵢₙ = ℓ√[2Pᵣ/(FᵧBN·factor)]. The factor is 0.90 for LRFD and 1/1.67 for ASD. Compare the theoretical minimum to the selected plate thickness and check the concrete bearing separately.