Use a positive moment gradient with supplied Cᵦ and compare a service-level design demand to Mₙ/1.67.
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
ANSI/AISC 360-22F1 · F2
Inputs
ASD
Use loads and strengths from the selected method. Re-enter values after switching methods.
LTB strength curve
Within modeled limits
Yield limit Lₚ
5.369ft
LTB limit Lᵣ
15.231ft
Nominal Mₙ
243.943kip-ft
Cᵦ factor
1.17
The point marks the entered Lᵦ. Colored bands separate yielding, inelastic LTB, and elastic LTB. The curve is capped at Mₚ.
Calculation results
Limit state
Demand
Available
Use
Major-axis bending
105 kip-ft
146.074 kip-ft
71.9%
Calculation values
Bracing zone
Inelastic LTB
Plastic moment Mₚ
266.667 kip-ft
Elastic Fcr
—
Available bending · LRFD
219.549 kip-ft
Available bending · ASD
146.074 kip-ft
SteelBeamLab / AISC 360-22 F1 · F2
W16×36 allowable moment in ASD
ASD · US customary
For compact, doubly symmetric I-sections with restrained ends at the braced segment. Classify the flange and web per Table B4.1b before selecting Compact. Verify brace stiffness, load height, and the moment diagram.
Entered values
Unbraced length Lᵦ
11 ft
Required moment Mᵣ
105 kip-ft
Flange and web class
Both compact
Steel yield stress Fᵧ
50 ksi
Elastic modulus Sₓ
56.5 in³
Plastic modulus Zₓ
64 in³
Minor-axis radius rᵧ
1.52 in
Effective radius rₜₛ
1.83 in
Torsion constant J
0.545 in⁴
Flange centroid spacing h₀
15.47 in
Cᵦ input method
Direct Cᵦ
Entered Cᵦ
1.17
Key results
Yield limit Lₚ
5.369ft
LTB limit Lᵣ
15.231ft
Nominal Mₙ
243.943kip-ft
Cᵦ factor
1.17
Limit-state screening
Limit state
Demand
Available
Use
Major-axis bending
105 kip-ft
146.074 kip-ft
71.9%
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
Worked solution at the starting values
Use Cᵦ = 1.17 from the chosen input method.
Calculate Lₚ = 5.369 ft and Lᵣ = 15.231 ft. The entered length is in Zone 2.
Calculate nominal bending strength 243.943 kip-ft and apply the selected design factor to obtain 146.074 kip-ft.
Calculation basis
For compact, doubly symmetric I-sections with restrained ends at the braced segment. Classify the flange and web per Table B4.1b before selecting Compact. Verify brace stiffness, load height, and the moment diagram.
Moment gradient
F1-1 gives Cᵦ = 12.5Mmax/(2.5Mmax + 3Mᴀ + 4Mʙ + 3Mᴄ). Use absolute moments within the same braced segment. An all-zero moment diagram uses Cᵦ = 1.0.
Zone transitions
F2-5 and F2-6 set Lₚ and Lᵣ using rᵧ, rₜₛ, J, Sₓ, h₀, Fᵧ, and E. For doubly symmetric I-sections, c = 1. Supply rₜₛ from the section table or calculate rₜₛ = √(√(IᵧCw)/Sₓ).
Bending strength
F2-1 applies plastic yielding at Lᵦ ≤ Lₚ. F2-2 interpolates between Mₚ and 0.7FᵧSₓ, with Cᵦ and the cap at Mₚ. Beyond Lᵣ, F2-3 and F2-4 use the elastic LTB stress times Sₓ with the same cap.