Thicker frost-resistant structure

Test a comparatively deep non-frost-susceptible structure at a modest freezing index.

Design readout

Powell Mᵣ
9,668.7
psi
Support k
630.7
pci
Frost depth
20.38
in
Depth margin
25.62
in

Frost penetration profile

Frost penetration profileTHERMAL PROFILEDEPTH BELOW SURFACERESISTANT DEPTH46 inFROST FRONT20.38 inSURFACE INDEX364 °F·daysBARE K498.4 pciCOMPOSITE K630.7 pci
Both depths are measured from the surface. The frost model uses one equivalent thermal material.

Review composite support

Subbase modulus is outside the FHWA guidance of 15–50 ksi and less than 4 × roadbed modulus. Marker shows resistant depth relative to modeled frost depth.

Calculation ledger
Linear CBR modulus E
12,000 psi
Bare subgrade k from Powell modulus
498.39 pci
Uncorrected Stefan depth
26.12 in
Surface freezing index
364 °F·days

Inputs

Changes update results

Subgrade and pavement
%
%
lb/ft³
in
in
ksi
Thermal assumptions
°F·days
Btu/(h·ft·°F)

Set λ to 1 for the Stefan result. Calibrate the thermal inputs using local data.

Work through this example

  1. Compare two CBR-to-modulus correlations for the soaked soil.
  2. Use Powell Mᵣ with granular subbase thickness and stiffness to estimate composite k.
  3. Compute frost depth from the surface freezing index, conductivity and soil water, then compare with the resistant section.

Reduce the resistant depth until the frost margin crosses zero.

The linear CBR correlation is a low-CBR fine-soil screen. Composite k uses the FHWA chart range for thickness and roadbed stiffness and omits seasonal, erosion and bedrock corrections. Use measured support and a layered thermal analysis where warranted.

Read the equations and sources