Methods and references

Each calculator shows its equations, assumptions and worked cases. These are the unit and review conventions shared by the suite.

Units and reference conditions

Inputs are retained in an internal SI basis when switching displays. CFM and m³/h describe actual volumetric flow. Solvent dilution uses SCFM at 60 °F and Nm³/h at 0 °C, both at 101.325 kPa, so the standard-flow conversion includes temperature.

One foot is 0.3048 m. One US gallon is 3.785411784 L. One conventional inch of water gauge is 249.08891 Pa. Absolute temperatures have an offset. Degree-hours scale by 5/9 from °F·h to °C·h. MMBtu is displayed as an energy equivalent of kWh.

Reading the diagrams and limits

Cerulean denotes supply, transfer or measured flow. Emerald marks filtered flow or a modeled operating region. Amber marks a limit or a point that needs review. Numerical results and entered assumptions are also available in the result tables or downloads.

ISO values distinguish the mathematical curve from ISO 14644-1:2015 Table 1 applicability. ACH and nominal FFU coverage are design quantities. ACGIH-style velocity and loading bands are screening aids and depend on equipment and contaminants. The NFPA 86 calculator uses a single-solvent LEL model with explicit reference conditions.

For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.

Calculator methods