NFPA 86 solvent vapor dilution

Estimate solvent vapor generation, minimum fresh-air dilution and margin to the entered LEL target.

Inputs

Solvent release
gal/h
Dilution settings
°F
ft
SCFM
Enter standardized flow. The results show its equivalent at process conditions.

Live results

Vapor concentration versus dilution airflow

Vapor concentration versus dilution airflowMIN. FRESH AIR122SCFMVAPOR FLOW0.7177SCFMAT AVAIL. FLOW6.1% LELLEL MARGIN+18.9ppModeled concentrationTarget 25% LEL100%0%Fresh airflow (log scale)Available airflow concentration0% LEL6.1% LELMax 25% LEL
The curve represents a well-mixed single-solvent estimate. The shaded region is at or below the modeled LEL target.

Available fresh air meets the modeled dilution target.

Min. fresh air
122.005 SCFM
Vapor flow
0.717696 SCFM
At avail. flow
6.10027 % LEL
LEL margin
+18.8997 pp

Vapor and input properties

Molecular weight
58.1 g/mol
Liquid specific gravity
0.79
Reference LEL
2.5 % vol
Vapor mass rate
6.59287 lb/h
Vapor at process conditions
0.927618 ACFM

Dilution and margin

Theoretical airflow at reference LEL
28.7078 SCFM
Temperature multiplier
1.06247 ×
Temperature-adjusted LEL
2.353 % vol
Screening factor
4 ×
Target concentration
25 % LEL
Concentration at calculated minimum
25 % LEL
Available fresh air
500 SCFM

Actual airflow at the oven

Estimated ambient pressure
101.325 kPa abs
Minimum actual fresh air
157.691 ACFM
Equivalent actual available air
646.247 ACFM

Equations and assumptions

Vapor generation

ṁ = SG × 1000 × V̇_liq · Q_v = (ṁ ÷ MW) × R × T ÷ P

Use liquid flow in m³/s and molecular weight in kg/mol. SCFM uses 60 °F at 1 atm. Nm³/h uses 0 °C at 1 atm. Use SDS data and the maximum credible evaporation rate.

Actual airflow at the oven

Q_actual = Q_normal × (T_process ÷ 273.15 K) × (101325 Pa ÷ P_site)

P_site is estimated from site elevation using a standard troposphere and assumes the oven is near ambient pressure. Convert minimum dilution and available air to the same conditions before comparing. Altitude affects actual volume for a given standardized flow.

Temperature and dilution

Q₁₀₀ = Q_v ÷ LEL₀ · Q_min = Q₁₀₀ × F × M_T

LEL₀ is a volume fraction at the reference condition. The estimated multiplier is 1/[1 − 0.000784 × max(T_C − 25, 0)]. A verified multiplier can be entered for the specific application. Use a compatible reference condition for Q_v and Q_min.

LEL screening and margin

%LEL = 100 × Q₁₀₀ × M_T ÷ Q_available · target = 100 ÷ F

The model takes fresh air as the mixture dilution volume for a conservative estimate. F = 4 gives a 25% LEL continuous screening target. A batch factor is a user-defined engineering screen. Batch schedules, code calculations and controls must be assessed for the adopted edition.

Application boundaries

One solvent · perfect mixing · complete evaporation

Verify site pressure and solvent-specific LEL at process conditions. Assess mixtures, combustion products, peak batch release profiles, purge, detection and interlocks separately. LEL (also called LFL) addresses flammability. Exposure limits require their own industrial hygiene evaluation.

References

Worked examples