HEPA / ULPA filter lifecycle cost

Compare filtration power, replacement spend and the modeled economic change-out pressure drop.

Inputs

Airflow & filter loading
CFM
in.wg
in.wg
in.wg/1k h
Pressure rise per 1,000 operating hours at rated flow.
%
Operating & replacement cost
/kWh
h
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Filter loading and annual cost curve

Filter loading and annual cost curveAVG. FAN POWER0.1652kWANNUAL ENERGY206.1USDANNUAL CHANGES397.1USDECONOMIC ΔP1.606in.wgFilter loading over timeTotal annual costClean2,750 hChange-out ΔPEconomic pressure vs change-out capClean 0.5018 in.wg1.606 in.wgCap 1.606 in.wg
The loading plot shows pressure rise across the modeled cycle. The cost curve combines energy with annualized replacement spend.

The modeled economic choice is bounded by the entered change-out cap.

Avg. fan power
0.165182 kW
Annual energy
206.147 USD
Annual changes
397.091 USD
Economic ΔP
1.60585 in.wg

Current change-out

Average filter pressure drop
1.05384 in.wg
Extra power from loading
0.0865237 kW
Operating hours per filter
2,750 h
Annual filtration energy
4.39626 MMBtu
Total current annual cost
603.238 USD

Economic threshold

Unconstrained change-out
2.61896 in.wg
Constrained change-out
1.60585 in.wg
Optimal operating hours per filter
2,750 h
Optimized annual cost
603.238 USD
Modeled annual savings
0 USD

Equations and assumptions

Average filtration power

ΔP_avg = ΔP_clean + x ÷ 2 · kW = Q × ΔP_avg ÷ (1000 × η)

x is the allowed pressure rise above clean. Q is m³/s and pressure is Pa. Constant airflow, uniform loading and fixed combined efficiency are assumed.

Annualized cost

C_year = H × [kW × c + C_r × r ÷ x]

H is annual operating hours, c is price per kWh, C_r is hardware plus labor per change and r is the measured pressure rise per operating hour. Expected changes per year can be fractional.

Economic change-out pressure

x* = √(2 × C_r × r ÷ [c × Q ÷ (1000 × η)])

Add x* to the clean pressure for the unconstrained threshold. The selected economic change-out is capped by the entered pressure limit. Validate system airflow, leaks, efficiency, contamination, service life and manufacturer limits with field measurements.