CleanroomVentLab · Calculation sheet · US customary
NFPA 86 solvent vapor dilution
Inputs
- Solvent
- Acetone
- Peak evaporation rate
- 1 gal/h
- Process basis
- Continuous · 4× (25% LEL)
- Process air temperature
- 212 °F
- Site elevation above sea level
- 0 ft
- Temperature correction
- Estimate from temperature
- Available fresh air
- 500 SCFM
Results
- Min. fresh air
- 122.005 SCFM
- Vapor flow
- 0.717696 SCFM
- At avail. flow
- 6.10027 % LEL
- LEL margin
- +18.8997 pp
- Molecular weight
- 58.1 g/mol
- Liquid specific gravity
- 0.79
- Reference LEL
- 2.5 % vol
- Vapor mass rate
- 6.59287 lb/h
- Vapor at process conditions
- 0.927618 ACFM
- Theoretical airflow at reference LEL
- 28.7078 SCFM
- Temperature multiplier
- 1.06247 ×
- Temperature-adjusted LEL
- 2.353 % vol
- Screening factor
- 4 ×
- Target concentration
- 25 % LEL
- Concentration at calculated minimum
- 25 % LEL
- Available fresh air
- 500 SCFM
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 157.691 ACFM
- Equivalent actual available air
- 646.247 ACFM
Available fresh air meets the modeled dilution target.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.