Custom SDS batch solvent

A hypothetical SDS supplies a molecular weight, liquid specific gravity and reference LEL for a short batch peak.

Inputs

Solvent release
g/mol
% vol
L/h
Dilution settings
×
°C
m
Nm³/h
Enter standardized flow. The results show its equivalent at process conditions.

Live results

Vapor concentration versus dilution airflow

Vapor concentration versus dilution airflowMIN. FRESH AIR523.4Nm³/hVAPOR FLOW1.282Nm³/hAT AVAIL. FLOW9.086% LELLEL MARGIN+3.414ppModeled concentrationTarget 12.5% LEL50%0%Fresh airflow (log scale)Available airflow concentration0% LEL9.086% LELMax 12.5% LEL
The curve represents a well-mixed single-solvent estimate. The shaded region is at or below the modeled LEL target.

Available fresh air meets the modeled dilution target.

Batch results use the entered peak rate and screening factor. Review the time-dependent release and applicable batch method.

Min. fresh air
523.353 Nm³/h
Vapor flow
1.28225 Nm³/h
At avail. flow
9.08599 % LEL
LEL margin
+3.41401 pp

Vapor and input properties

Molecular weight
88.1 g/mol
Liquid specific gravity
0.9
Reference LEL
2.1 % vol
Vapor mass rate
5.04 kg/h
Vapor at process conditions
1.79863 m³/h

Dilution and margin

Theoretical airflow at reference LEL
61.0596 Nm³/h
Temperature multiplier
1.0714 ×
Temperature-adjusted LEL
1.96006 % vol
Screening factor
8 ×
Target concentration
12.5 % LEL
Concentration at calculated minimum
12.5 % LEL
Available fresh air
720 Nm³/h

Actual airflow at the oven

Estimated ambient pressure
101.325 kPa abs
Minimum actual fresh air
734.112 m³/h
Equivalent actual available air
1,009.95 m³/h

Worked calculation at the starting values

Changing the SDS properties changes vapor generation and dilution independently. Confirm the physical property basis on the current SDS.

  1. Vapor generation = 1.282252 Nm³/h from 5.04 kg/h.
  2. Minimum dilution = 61.05962 × 8 × 1.071398 = 523.3532 Nm³/h.
  3. LEL margin = 12.5 − 9.085994 = 3.414006 percentage points.
Starting result snapshot
Min. fresh air
523.353 Nm³/h
Vapor flow
1.28225 Nm³/h
At avail. flow
9.08599 % LEL
LEL margin
+3.41401 pp

Equations and assumptions

Vapor generation

ṁ = SG × 1000 × V̇_liq · Q_v = (ṁ ÷ MW) × R × T ÷ P

Use liquid flow in m³/s and molecular weight in kg/mol. SCFM uses 60 °F at 1 atm. Nm³/h uses 0 °C at 1 atm. Use SDS data and the maximum credible evaporation rate.

Actual airflow at the oven

Q_actual = Q_normal × (T_process ÷ 273.15 K) × (101325 Pa ÷ P_site)

P_site is estimated from site elevation using a standard troposphere and assumes the oven is near ambient pressure. Convert minimum dilution and available air to the same conditions before comparing. Altitude affects actual volume for a given standardized flow.

Temperature and dilution

Q₁₀₀ = Q_v ÷ LEL₀ · Q_min = Q₁₀₀ × F × M_T

LEL₀ is a volume fraction at the reference condition. The estimated multiplier is 1/[1 − 0.000784 × max(T_C − 25, 0)]. A verified multiplier can be entered for the specific application. Use a compatible reference condition for Q_v and Q_min.

LEL screening and margin

%LEL = 100 × Q₁₀₀ × M_T ÷ Q_available · target = 100 ÷ F

The model takes fresh air as the mixture dilution volume for a conservative estimate. F = 4 gives a 25% LEL continuous screening target. A batch factor is a user-defined engineering screen. Batch schedules, code calculations and controls must be assessed for the adopted edition.

Application boundaries

One solvent · perfect mixing · complete evaporation

Verify site pressure and solvent-specific LEL at process conditions. Assess mixtures, combustion products, peak batch release profiles, purge, detection and interlocks separately. LEL (also called LFL) addresses flammability. Exposure limits require their own industrial hygiene evaluation.

References

More worked examples

Open calculator defaults