o-Xylene with low fresh airflow
Inputs
- Solvent
- o-Xylene
- Peak evaporation rate
- 12 L/h
- Process basis
- Continuous · 4× (25% LEL)
- Process air temperature
- 210 °C
- Site elevation above sea level
- 0 m
- Temperature correction
- Estimate from temperature
- Available fresh air
- 230 Nm³/h
Results
- Min. fresh air
- 1,158.59 Nm³/h
- Vapor flow
- 2.22873 Nm³/h
- At avail. flow
- 125.934 % LEL
- LEL margin
- -100.934 pp
- Molecular weight
- 106.2 g/mol
- Liquid specific gravity
- 0.88
- Reference LEL
- 0.9 % vol
- Vapor mass rate
- 10.56 kg/h
- Vapor at process conditions
- 3.9422 m³/h
- Theoretical airflow at reference LEL
- 247.637 Nm³/h
- Temperature multiplier
- 1.16965 ×
- Temperature-adjusted LEL
- 0.769464 % vol
- Screening factor
- 4 ×
- Target concentration
- 25 % LEL
- Concentration at calculated minimum
- 25 % LEL
- Available fresh air
- 230 Nm³/h
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 2,049.32 m³/h
- Equivalent actual available air
- 406.826 m³/h
Available fresh air is below the modeled target.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.