o-Xylene with low fresh airflow

A hot o-xylene process is screened against a deliberately low available airflow.

Inputs

Solvent release
L/h
Dilution settings
°C
m
Nm³/h
Enter standardized flow. The results show its equivalent at process conditions.

Live results

Vapor concentration versus dilution airflow

Vapor concentration versus dilution airflowMIN. FRESH AIR1,159Nm³/hVAPOR FLOW2.229Nm³/hAT AVAIL. FLOW125.9% LELLEL MARGIN-100.9ppModeled concentrationTarget 25% LEL100%0%Fresh airflow (log scale)Available airflow concentration0% LEL125.9% LELMax 25% LEL
The curve represents a well-mixed single-solvent estimate. The shaded region is at or below the modeled LEL target.

Available fresh air is below the modeled target.

Min. fresh air
1,158.59 Nm³/h
Vapor flow
2.22873 Nm³/h
At avail. flow
125.934 % LEL
LEL margin
-100.934 pp

Vapor and input properties

Molecular weight
106.2 g/mol
Liquid specific gravity
0.88
Reference LEL
0.9 % vol
Vapor mass rate
10.56 kg/h
Vapor at process conditions
3.9422 m³/h

Dilution and margin

Theoretical airflow at reference LEL
247.637 Nm³/h
Temperature multiplier
1.16965 ×
Temperature-adjusted LEL
0.769464 % vol
Screening factor
4 ×
Target concentration
25 % LEL
Concentration at calculated minimum
25 % LEL
Available fresh air
230 Nm³/h

Actual airflow at the oven

Estimated ambient pressure
101.325 kPa abs
Minimum actual fresh air
2,049.32 m³/h
Equivalent actual available air
406.826 m³/h

Worked calculation at the starting values

The entered fresh-air rate leaves the model above target. Review the negative LEL margin and the chart crossing.

  1. Vapor generation = 2.228734 Nm³/h from 10.56 kg/h.
  2. Minimum dilution = 247.6371 × 4 × 1.169645 = 1,158.59 Nm³/h.
  3. LEL margin = 25 − 125.9337 = -100.9337 percentage points.
Starting result snapshot
Min. fresh air
1,158.59 Nm³/h
Vapor flow
2.22873 Nm³/h
At avail. flow
125.934 % LEL
LEL margin
-100.934 pp

Equations and assumptions

Vapor generation

ṁ = SG × 1000 × V̇_liq · Q_v = (ṁ ÷ MW) × R × T ÷ P

Use liquid flow in m³/s and molecular weight in kg/mol. SCFM uses 60 °F at 1 atm. Nm³/h uses 0 °C at 1 atm. Use SDS data and the maximum credible evaporation rate.

Actual airflow at the oven

Q_actual = Q_normal × (T_process ÷ 273.15 K) × (101325 Pa ÷ P_site)

P_site is estimated from site elevation using a standard troposphere and assumes the oven is near ambient pressure. Convert minimum dilution and available air to the same conditions before comparing. Altitude affects actual volume for a given standardized flow.

Temperature and dilution

Q₁₀₀ = Q_v ÷ LEL₀ · Q_min = Q₁₀₀ × F × M_T

LEL₀ is a volume fraction at the reference condition. The estimated multiplier is 1/[1 − 0.000784 × max(T_C − 25, 0)]. A verified multiplier can be entered for the specific application. Use a compatible reference condition for Q_v and Q_min.

LEL screening and margin

%LEL = 100 × Q₁₀₀ × M_T ÷ Q_available · target = 100 ÷ F

The model takes fresh air as the mixture dilution volume for a conservative estimate. F = 4 gives a 25% LEL continuous screening target. A batch factor is a user-defined engineering screen. Batch schedules, code calculations and controls must be assessed for the adopted edition.

Application boundaries

One solvent · perfect mixing · complete evaporation

Verify site pressure and solvent-specific LEL at process conditions. Assess mixtures, combustion products, peak batch release profiles, purge, detection and interlocks separately. LEL (also called LFL) addresses flammability. Exposure limits require their own industrial hygiene evaluation.