Ethanol at room temperature

Ethanol evaporation is modeled at 22 °C under continuous release.

Inputs

Solvent release
gal/h
Dilution settings
°F
ft
SCFM
Enter standardized flow. The results show its equivalent at process conditions.

Live results

Vapor concentration versus dilution airflow

Vapor concentration versus dilution airflowMIN. FRESH AIR87.71SCFMVAPOR FLOW0.7236SCFMAT AVAIL. FLOW6.265% LELLEL MARGIN+18.73ppModeled concentrationTarget 25% LEL100%0%Fresh airflow (log scale)Available airflow concentration0% LEL6.265% LELMax 25% LEL
The curve represents a well-mixed single-solvent estimate. The shaded region is at or below the modeled LEL target.

Available fresh air meets the modeled dilution target.

Min. fresh air
87.7106 SCFM
Vapor flow
0.723612 SCFM
At avail. flow
6.26504 % LEL
LEL margin
+18.735 pp

Vapor and input properties

Molecular weight
46.1 g/mol
Liquid specific gravity
0.79
Reference LEL
3.3 % vol
Vapor mass rate
5.2743 lb/h
Vapor at process conditions
0.739765 ACFM

Dilution and margin

Theoretical airflow at reference LEL
21.9276 SCFM
Temperature multiplier
1 ×
Temperature-adjusted LEL
3.3 % vol
Screening factor
4 ×
Target concentration
25 % LEL
Concentration at calculated minimum
25 % LEL
Available fresh air
350 SCFM

Actual airflow at the oven

Estimated ambient pressure
101.325 kPa abs
Minimum actual fresh air
89.6684 ACFM
Equivalent actual available air
357.813 ACFM

Worked calculation at the starting values

The automatic temperature multiplier is 1 at or below the 25 °C reference. US standard and normal SI flows use different temperatures.

  1. Vapor generation = 1.163183 Nm³/h from 2.39238 kg/h.
  2. Minimum dilution = 35.24797 × 4 × 1 = 140.9919 Nm³/h.
  3. LEL margin = 25 − 6.26504 = 18.73496 percentage points.
Starting result snapshot
Min. fresh air
87.7106 SCFM
Vapor flow
0.723612 SCFM
At avail. flow
6.26504 % LEL
LEL margin
+18.735 pp

Equations and assumptions

Vapor generation

ṁ = SG × 1000 × V̇_liq · Q_v = (ṁ ÷ MW) × R × T ÷ P

Use liquid flow in m³/s and molecular weight in kg/mol. SCFM uses 60 °F at 1 atm. Nm³/h uses 0 °C at 1 atm. Use SDS data and the maximum credible evaporation rate.

Actual airflow at the oven

Q_actual = Q_normal × (T_process ÷ 273.15 K) × (101325 Pa ÷ P_site)

P_site is estimated from site elevation using a standard troposphere and assumes the oven is near ambient pressure. Convert minimum dilution and available air to the same conditions before comparing. Altitude affects actual volume for a given standardized flow.

Temperature and dilution

Q₁₀₀ = Q_v ÷ LEL₀ · Q_min = Q₁₀₀ × F × M_T

LEL₀ is a volume fraction at the reference condition. The estimated multiplier is 1/[1 − 0.000784 × max(T_C − 25, 0)]. A verified multiplier can be entered for the specific application. Use a compatible reference condition for Q_v and Q_min.

LEL screening and margin

%LEL = 100 × Q₁₀₀ × M_T ÷ Q_available · target = 100 ÷ F

The model takes fresh air as the mixture dilution volume for a conservative estimate. F = 4 gives a 25% LEL continuous screening target. A batch factor is a user-defined engineering screen. Batch schedules, code calculations and controls must be assessed for the adopted edition.

Application boundaries

One solvent · perfect mixing · complete evaporation

Verify site pressure and solvent-specific LEL at process conditions. Assess mixtures, combustion products, peak batch release profiles, purge, detection and interlocks separately. LEL (also called LFL) addresses flammability. Exposure limits require their own industrial hygiene evaluation.

References

More worked examples

Open calculator defaults