CleanroomVentLab · Calculation sheet · Metric SI
Custom SDS batch solvent
Inputs
- Solvent
- Custom solvent from SDS
- Molecular weight
- 88.1 g/mol
- Liquid specific gravity
- 0.9
- LEL at reference conditions
- 2.1 % vol
- Peak evaporation rate
- 5.6 L/h
- Process basis
- Batch · screening factor
- Batch screening factor
- 8 ×
- Process air temperature
- 110 °C
- Site elevation above sea level
- 0 m
- Temperature correction
- Estimate from temperature
- Available fresh air
- 720 Nm³/h
Results
- Min. fresh air
- 523.353 Nm³/h
- Vapor flow
- 1.28225 Nm³/h
- At avail. flow
- 9.08599 % LEL
- LEL margin
- +3.41401 pp
- Molecular weight
- 88.1 g/mol
- Liquid specific gravity
- 0.9
- Reference LEL
- 2.1 % vol
- Vapor mass rate
- 5.04 kg/h
- Vapor at process conditions
- 1.79863 m³/h
- Theoretical airflow at reference LEL
- 61.0596 Nm³/h
- Temperature multiplier
- 1.0714 ×
- Temperature-adjusted LEL
- 1.96006 % vol
- Screening factor
- 8 ×
- Target concentration
- 12.5 % LEL
- Concentration at calculated minimum
- 12.5 % LEL
- Available fresh air
- 720 Nm³/h
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 734.112 m³/h
- Equivalent actual available air
- 1,009.95 m³/h
Available fresh air meets the modeled dilution target. Batch results use the entered peak rate and screening factor. Review the time-dependent release and applicable batch method.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.
https://calcsheetlab.com/cleanroomventlab/nfpa-86-solvent-vapor-dilution-calculator/custom-sds-batch/