CleanroomVentLab · Calculation sheet · US customary
Ethanol at room temperature
Inputs
- Solvent
- Ethanol
- Peak evaporation rate
- 0.8 gal/h
- Process basis
- Continuous · 4× (25% LEL)
- Process air temperature
- 71.6 °F
- Site elevation above sea level
- 0 ft
- Temperature correction
- Estimate from temperature
- Available fresh air
- 350 SCFM
Results
- Min. fresh air
- 87.7106 SCFM
- Vapor flow
- 0.723612 SCFM
- At avail. flow
- 6.26504 % LEL
- LEL margin
- +18.735 pp
- Molecular weight
- 46.1 g/mol
- Liquid specific gravity
- 0.79
- Reference LEL
- 3.3 % vol
- Vapor mass rate
- 5.2743 lb/h
- Vapor at process conditions
- 0.739765 ACFM
- Theoretical airflow at reference LEL
- 21.9276 SCFM
- Temperature multiplier
- 1 ×
- Temperature-adjusted LEL
- 3.3 % vol
- Screening factor
- 4 ×
- Target concentration
- 25 % LEL
- Concentration at calculated minimum
- 25 % LEL
- Available fresh air
- 350 SCFM
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 89.6684 ACFM
- Equivalent actual available air
- 357.813 ACFM
Available fresh air meets the modeled dilution target.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.