Worked example · Product cooling

Hardening already-frozen meat

A staging freezer lowers the core temperature of product that arrives fully frozen.

Pull-down time
0.27h
Heat removed
17,136kJ
Effective rate
17.4kW
Freeze time
0h
Edit inputs

Inputs

Edit any value to recalculate.

Batch & temperatures
kg
°C
°C
°C
Product properties
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
Equipment

Enter refrigeration output at the actual operating condition. The percentage is the share available to remove product heat.

kW
%

Core temperature pull-down

Core temperature pull-downA constant effective capacity turns each sensible or latent heat term into the length of its stage.Core temperature / °CElapsed time / h00.10.10.20.3-29-22-15-8Above freezePhase changeBelow freeze

A constant effective capacity turns each sensible or latent heat term into the length of its stage.

Calculation breakdown

Sensible heat above freezing
0kJ
Heat of fusion
0kJ
Sensible heat below freezing
17,136kJ
Heat per unit mass
28.56kJ/kg
Time above freezing
0h
Time below freezing
0.27h

Work through this case

  1. Sensible heat below freezing 17,136kJ
  2. Heat of fusion 0kJ
  3. Pull-down time 0.27h

Changing latent heat does not change this case. The frozen specific heat and the available equipment capacity drive the estimate.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Three-stage batch enthalpy

Etotal = m × c₊ΔT₊ + m × Lf + m × c₋ΔT₋

The sensible terms use temperature changes above and below the freezing point. A batch starting below freezing uses only the last term. A batch stopping at the freezing point ends before the latent stage in this model.

Estimated core pull-down

t = Etotal / (3,600 × Qrated × effectiveness)

For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.

References

Questions and answers

What should I check in the hardening already-frozen meat example?

Changing latent heat does not change this case. The frozen specific heat and the available equipment capacity drive the estimate.