A constant effective capacity turns each sensible or latent heat term into the length of its stage.
Calculation breakdown
Sensible heat above freezing
0kJ
Heat of fusion
0kJ
Sensible heat below freezing
35,475kJ
Heat per unit mass
47.3kJ/kg
Time above freezing
0h
Time below freezing
0.84h
Work through this case
Effective rate11.76kW
Sensible heat below freezing35,475kJ
Pull-down time0.84h
Use measured enthalpy if additional product water freezes over this range. The simple three-stage model treats product already below its nominal freezing point as frozen.
More worked examples
Open a case with its assumptions loaded, then edit the inputs.
The sensible terms use temperature changes above and below the freezing point. A batch starting below freezing uses only the last term. A batch stopping at the freezing point ends before the latent stage in this model.
Estimated core pull-down
t = Etotal / (3,600 × Qrated × effectiveness)
For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.
What should I check in the ice cream tub hardening example?
Use measured enthalpy if additional product water freezes over this range. The simple three-stage model treats product already below its nominal freezing point as frozen.
ColdChainLab · Engineering calculation
Ice cream tub hardening
Metric SI · https://calcsheetlab.com/coldchainlab/blast-chiller-freezing-time/ice-cream-tub-hardening/
Inputs
Batch mass
750 kg
Initial core temperature
-6 °C
Target core temperature
-28 °C
Product freeze point
-2.5 °C
Specific heat above freezing
3.65 kJ/(kg·K)
Specific heat below freezing
2.15 kJ/(kg·K)
Latent heat of fusion
252 kJ/kg
Rated refrigeration capacity
28 kW
Effective batch capacity
42 %
Results
Pull-down time
0.84h
Heat removed
35,475kJ
Effective rate
11.76kW
Freeze time
0h
Sensible heat above freezing
0kJ
Heat of fusion
0kJ
Sensible heat below freezing
35,475kJ
Heat per unit mass
47.3kJ/kg
Time above freezing
0h
Time below freezing
0.84h
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.