Worked example · Field diagnostics

R-290 self-contained display cabinet

A commercial cabinet charged with propane is evaluated with an absolute-pressure instrument.

Superheat
8.69K
Subcooling
6.76K
Suction dew
-13.69°C
Liquid bubble
37.76°C
Edit inputs

Inputs

Edit any value to recalculate.

Refrigerant & pressure basis

For gauge readings, enter local barometric pressure. Each pressure and temperature pair should come from the same line location.

Measured line conditions
kPa(a)
°C
kPa(a)
°C

Saturation pressure–temperature

Saturation pressure–temperatureThe operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.Pressure / kPa(a) (log scale)Temperature / °C-75.1-33.87.548.890.1331496833,132SH 8.7 KSC 6.8 KSaturationLiquid measurement

The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.

Calculation breakdown

Suction bubble point
-13.69°C
Liquid dew point
37.76°C
Suction temperature glide
0K
Liquid temperature glide
0K
Absolute suction pressure
305kPa(a)
Absolute liquid pressure
1,300kPa(a)
Supported absolute pressure range
32.5–3,131.9kPa(a)

Work through this case

  1. Suction dew -13.69°C
  2. Superheat 8.69K
  3. Subcooling 6.76K

Use only approved service procedures for flammable refrigerant. Compare the line temperatures with the same propane saturation curve at two different pressures.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Gauge and absolute pressure

Pabsolute = Pgauge + Plocal atmosphere

The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.

Superheat and subcooling

SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line

Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.

Saturation curves

P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]

The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.

References

Questions and answers

What should I check in the r-290 self-contained display cabinet example?

Use only approved service procedures for flammable refrigerant. Compare the line temperatures with the same propane saturation curve at two different pressures.