Worked example · Field diagnostics

R-410A high-pressure refrigeration

A process refrigeration circuit has a high-side operating pressure representative of R-410A service.

Superheat
7.72K
Subcooling
8.02K
Suction dew
-0.72°C
Liquid bubble
46.02°C
Edit inputs

Inputs

Edit any value to recalculate.

Refrigerant & pressure basis

For gauge readings, enter local barometric pressure. Each pressure and temperature pair should come from the same line location.

Measured line conditions
kPa(a)
°C
kPa(a)
°C

Saturation pressure–temperature

Saturation pressure–temperatureThe operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.Pressure / kPa(a) (log scale)Temperature / °C-74.1-3703774.1482159594,276SH 7.7 KSC 8 KDew / vaporBubble / liquid

The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.

Calculation breakdown

Suction bubble point
-0.82°C
Liquid dew point
46.14°C
Suction temperature glide
0.1K
Liquid temperature glide
0.12K
Absolute suction pressure
780kPa(a)
Absolute liquid pressure
2,800kPa(a)
Supported absolute pressure range
48.2–4,276.3kPa(a)

Work through this case

  1. Liquid temperature glide 0.12K
  2. Suction dew -0.72°C
  3. Subcooling 8.02K

Use the R-410A-specific saturation curve. The chart distinguishes its small glide from the longer temperature spans of the measured lines.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Gauge and absolute pressure

Pabsolute = Pgauge + Plocal atmosphere

The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.

Superheat and subcooling

SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line

Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.

Saturation curves

P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]

The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.

References

Questions and answers

What should I check in the r-410a high-pressure refrigeration example?

Use the R-410A-specific saturation curve. The chart distinguishes its small glide from the longer temperature spans of the measured lines.