The operating markers compare suction temperature with the dew line and liquid temperature with the bubble line. Pressure is plotted on a logarithmic scale.
Calculation breakdown
Suction bubble point
-35.65°C
Liquid dew point
34.99°C
Suction temperature glide
0K
Liquid temperature glide
0K
Absolute suction pressure
90kPa(a)
Absolute liquid pressure
1,350kPa(a)
Supported absolute pressure range
15.6–6,255.7kPa(a)
Work through this case
Absolute suction pressure90kPa(a)
Suction dew-35.65°C
Superheat7.65K
The gauge value is negative while absolute pressure remains positive. Verify the local atmosphere used in the conversion and the system safety procedure.
More worked examples
Open a case with its assumptions loaded, then edit the inputs.
The default atmosphere is 101.325 kPa or 14.696 psia. Select absolute pressure when the instrument already reports it. The model preserves the operating point when you change the pressure reference.
Superheat and subcooling
SH = Tsuction line − Tdew(Psuction) • SC = Tbubble(Pliquid) − Tliquid line
Vapor superheat uses the dew point. Liquid subcooling uses the bubble point. R-448A has appreciable glide, and R-404A and R-410A have separate liquid and vapor fits.
Saturation curves
P = Pc × exp[(Tc / T) × Σ ai × (1 − T / Tc)^bi]
The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.
What should I check in the r-717 ammonia vacuum suction example?
The gauge value is negative while absolute pressure remains positive. Verify the local atmosphere used in the conversion and the system safety procedure.
ColdChainLab · Engineering calculation
R-717 ammonia vacuum suction
Metric SI · https://calcsheetlab.com/coldchainlab/refrigerant-pt-superheat-subcooling/r717-ammonia-vacuum-suction/
Inputs
Refrigerant
R-717 (ammonia)
Pressure reference
Gauge pressure
Local barometric pressure
101.325 kPa(a)
Suction pressure
-11.325 kPa(g)
Suction line temperature
-28 °C
Liquid pressure
1248.675 kPa(g)
Liquid line temperature
26 °C
Results
Superheat
7.65K
Subcooling
8.99K
Suction dew
-35.65°C
Liquid bubble
34.99°C
Suction bubble point
-35.65°C
Liquid dew point
34.99°C
Suction temperature glide
0K
Liquid temperature glide
0K
Absolute suction pressure
90kPa(a)
Absolute liquid pressure
1,350kPa(a)
Supported absolute pressure range
15.6–6,255.7kPa(a)
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.