Coolant valve with negative process gain
Opening a cooling valve lowers the measured outlet temperature. The process gain carries that sign.
Model inputs
- Process gain Kp
- −1.3
- Time constant τp
- 25 s
- Dead time θ
- 5 s
- Tuning rule
- Skogestad SIMC
- Controller action
- PID
- Controller form
- Parallel
- Closed-loop time constant τc
- 8 s
Model inputs
Process reaction & setpoint response
Settled in model- P gain
- −1.5779
- I gain
- −0.0591721/s
- D gain
- −2.4655s
- Overshoot
- 0.90987%
Calculated results
- ISA Kc
- −1.5779
- ISA Ti
- 26.667s
- ISA Td
- 1.5625s
- Parallel Kp
- −1.5779
- Parallel Ki
- −0.0591721/s
- Parallel Kd
- −2.4655s
- Dead-time ratio θ/τ
- 0.2
- Overshoot
- 0.90987%
- 2% settling time
- 33.191s
- Peak |control effort|
- 1.8738
- Setpoint IAE
- 13.814s
- Steady state (model)
- 1
- Simulation step
- 0.125s
- Simulated window
- 255s
- Extended SIMC adds θ/3 as derivative time in the series form for an FOPDT model.
Model and interpretation
Full methodologyFit the process first
Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.
Match the controller form
SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.
Read the simulation window
The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.