ControlLoopLab
Home PID tuningWorked example

Steam jacket temperature PI

Steam valve movement reaches the jacket quickly, then the vessel temperature responds more slowly.

Model inputs

Process model
s
s
Controller
s

Process reaction & setpoint response

Settled in model
Kc
1.0833
Ti
78s
Td
0s
Overshoot
0.038775%
Open- and closed-loop FOPDT responseClosed-loop responseoutput0199398597796−0.080.3070.6941.08Time (s)Open-loop reactionoutput0199398597796−0.1440.5521.251.94Time (s)SetpointClosed-loop outputOpen-loop output
G(s) = Kp exp(−θs) / (1 + τp s)

Calculated results

ISA Kc
1.0833
ISA Ti
78s
ISA Td
0s
Parallel Kp
1.0833
Parallel Ki
0.0138891/s
Parallel Kd
0s
Dead-time ratio θ/τ
0.20513
Overshoot
0.038775%
2% settling time
86.555s
Peak |control effort|
1.3039
Setpoint IAE
40.016s
Steady state (model)
1
Simulation step
0.37494s
Simulated window
796s

Model and interpretation

Full methodology

Fit the process first

Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.

Match the controller form

SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.

Read the simulation window

The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.