Tank pH Cohen–Coon starting point
A mixing tank pH loop has a local process gain at one operating point and a visible delay after reagent changes.
Model inputs
- Process gain Kp
- 0.9
- Time constant τp
- 20 s
- Dead time θ
- 8 s
- Tuning rule
- Cohen–Coon
- Controller action
- PID
- Controller form
- Series (interacting)
Model inputs
Process reaction & setpoint response
Settled in model- Kc
- 3.1876
- Ti
- 13.6s
- Td
- 3.3873s
- Overshoot
- 68.873%
Calculated results
- Series Kc
- 3.1876
- Series Ti
- 13.6s
- Series Td
- 3.3873s
- ISA Kc
- 3.9815
- ISA Ti
- 16.988s
- ISA Td
- 2.7119s
- Parallel Kp
- 3.9815
- Parallel Ki
- 0.234371/s
- Parallel Kd
- 10.797s
- Dead-time ratio θ/τ
- 0.4
- Overshoot
- 68.873%
- 2% settling time
- 93.299s
- Peak |control effort|
- 5.8511
- Setpoint IAE
- 21.958s
- Steady state (model)
- 1
- Simulation step
- 0.068178s
- Simulated window
- 177.88s
- Reaction-curve rules are aggressive starting points. Compare effort and overshoot before commissioning.
Model and interpretation
Full methodologyFit the process first
Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.
Match the controller form
SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.
Read the simulation window
The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.