Coolant valve with negative process gain

Opening a cooling valve lowers the measured outlet temperature. The process gain carries that sign.

Model inputs

Process model
s
s
Controller
s

Process reaction & setpoint response

Settled in model
P gain
−1.5779
I gain
−0.0591721/s
D gain
−2.4655s
Overshoot
0.90987%
Open- and closed-loop FOPDT responseClosed-loop responseoutput063.8128191255−0.08070.3090.71.09Time (s)Open-loop reactionoutput063.8128191255−1.4−0.901−0.3990.104Time (s)SetpointClosed-loop outputOpen-loop output
G(s) = Kp exp(−θs) / (1 + τp s)

Calculated results

ISA Kc
−1.5779
ISA Ti
26.667s
ISA Td
1.5625s
Parallel Kp
−1.5779
Parallel Ki
−0.0591721/s
Parallel Kd
−2.4655s
Dead-time ratio θ/τ
0.2
Overshoot
0.90987%
2% settling time
33.191s
Peak |control effort|
1.8738
Setpoint IAE
13.814s
Steady state (model)
1
Simulation step
0.125s
Simulated window
255s
  • Extended SIMC adds θ/3 as derivative time in the series form for an FOPDT model.

Model and interpretation

Full methodology

Fit the process first

Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.

Match the controller form

SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.

Read the simulation window

The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.