ControlLoopLab
Home RTD & thermistorWorked example

Freezer Pt100 below zero

A platinum probe reads a cold chamber where the cubic Callendar–Van Dusen correction applies.

Model inputs

Sensor conversion
°C
RTD leads & excitation
m
mm²
°C
%
mA
°C/mW

Fractional AWG shows the equivalent copper area.

Calibration curves & sensor wiring

IEC nominal curve
Temperature
−70°C
Resistance
72.335Ω
2-wire error
4.8567°C
Self-heating
0.01302°C
Platinum and NTC calibrationCalibration curvesR / R₍₂₅₎−20062.53255888500.02050.3094.6770.5Sensor temperature (°C)IEC platinumNTC comparisonOperating pointLead-resistance offset2-wire1.94 Ω3-wire residual0.0194 Ω
R(T)/R₀ = 1 + AT + BT² + C(T − 100)T³ below 0 °C · C term is zero at and above 0 °C

Calculated results

Nominal temperature
−70°C
Sensing resistance
72.335Ω
Local sensitivity
0.4001Ω/°C
Single lead resistance
0.97066Ω
2-wire apparent resistance
74.276Ω
2-wire lead error
4.8567°C
3-wire apparent resistance
72.354Ω
3-wire mismatch error
0.048521°C
Sensor dissipation
0.02604mW
Self-heating error
0.01302°C

Model and interpretation

Full methodology

Use the nominal platinum curve

A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹². The nominal range is −200 to 850 °C. Actual probe tolerance, calibration coefficients and certified operating span come from its datasheet.

Budget wiring and self-heating separately

A 2-wire readout includes twice the lead resistance. For 3-wire compensation the residual is modeled as one lead resistance times the signed mismatch percentage. Self-heating is I²R times the supplied temperature rise per mW.

Use the correct sensor family

NTC conversion uses Beta or 1/TK = A + B ln R + C(ln R)³. The divider node sits between a pull-up and the grounded NTC. Thermocouple cold-junction compensation uses a different model and is outside this tool.