ControlLoopLab
Home RTD & thermistorWorked example

Pt100 two-point resistance check

A calibrated resistor substitutes for a Pt100 at the instrument terminals in a bench check.

Model inputs

Sensor conversion
Ω
RTD leads & excitation
m
mm²
°C
%
mA
°C/mW

Fractional AWG shows the equivalent copper area.

Calibration curves & sensor wiring

IEC nominal curve
Temperature
100°C
Resistance
138.51Ω
2-wire error
0°C
Self-heating
0.03989°C
Platinum and NTC calibrationCalibration curvesR / R₍₂₅₎−20062.53255888500.02050.3094.6770.5Sensor temperature (°C)IEC platinumNTC comparisonOperating pointLead-resistance offset2-wire0 Ω3-wire residual0 Ω
R(T)/R₀ = 1 + AT + BT² + C(T − 100)T³ below 0 °C · C term is zero at and above 0 °C

Calculated results

Nominal temperature
100°C
Sensing resistance
138.51Ω
Local sensitivity
0.37928Ω/°C
Single lead resistance
0Ω
2-wire apparent resistance
138.51Ω
2-wire lead error
0°C
3-wire apparent resistance
138.51Ω
3-wire mismatch error
0°C
Sensor dissipation
0.19945mW
Self-heating error
0.03989°C

Model and interpretation

Full methodology

Use the nominal platinum curve

A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹². The nominal range is −200 to 850 °C. Actual probe tolerance, calibration coefficients and certified operating span come from its datasheet.

Budget wiring and self-heating separately

A 2-wire readout includes twice the lead resistance. For 3-wire compensation the residual is modeled as one lead resistance times the signed mismatch percentage. Self-heating is I²R times the supplied temperature rise per mW.

Use the correct sensor family

NTC conversion uses Beta or 1/TK = A + B ln R + C(ln R)³. The divider node sits between a pull-up and the grounded NTC. Thermocouple cold-junction compensation uses a different model and is outside this tool.