ControlLoopLab
Home RTD & thermistorWorked example

Steinhart–Hart resistance inversion

A sensor calibration supplies three Steinhart–Hart coefficients for a wider thermistor fit.

Model inputs

Sensor conversion
Ω
Thermistor & divider
Ω
V

Calibration curves & sensor wiring

NTC model
Temperature
44.807°C
Resistance
4400Ω
Divider
1.9643V
Sensitivity
−46.694mV/°C
Platinum and NTC calibrationCalibration curvesR / R₍₂₅₎−401.2542.583.81250.01960.2824.0658.3Sensor temperature (°C)IEC platinumNTC comparisonOperating pointNTC dividerPull-up ↓VsupADC nodeVoutNTC ↓GND
R(T)/R₀ = 1 + AT + BT² + C(T − 100)T³ below 0 °C · C term is zero at and above 0 °C

Calculated results

Sensor temperature
44.807°C
NTC resistance
4400Ω
Divider node (NTC to ground)
1.9643V
Divider sensitivity
−46.694mV/°C
NTC reference at 25 °C
9999.9Ω
  • Use the sensor vendor’s coefficients and rated temperature range. The divider ignores ADC input loading and heating.

Model and interpretation

Full methodology

Use the nominal platinum curve

A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹². The nominal range is −200 to 850 °C. Actual probe tolerance, calibration coefficients and certified operating span come from its datasheet.

Budget wiring and self-heating separately

A 2-wire readout includes twice the lead resistance. For 3-wire compensation the residual is modeled as one lead resistance times the signed mismatch percentage. Self-heating is I²R times the supplied temperature rise per mW.

Use the correct sensor family

NTC conversion uses Beta or 1/TK = A + B ln R + C(ln R)³. The divider node sits between a pull-up and the grounded NTC. Thermocouple cold-junction compensation uses a different model and is outside this tool.