ControlLoopLab
Home 4–20 mA loopWorked example

HART check with a low-resistance AI card

An input card has enough voltage margin but contributes less resistance than a typical HART load.

Model inputs

Supply & wiring
V
V
Ω
Ω
m
mm²
°C
Current scaling
mA
EU
EU

Fractional AWG shows the equivalent copper area.

Two-wire circuit & voltage reserve

HART load below 250 Ω
Headroom
9.2155V
Loop load
126.57Ω
Scaled value
96EU
Input current
13.6mA
Two-wire circuit and transmitter voltagePowered two-wire loop22 mA checkDC supply24 VTransmitter21.2 VAI load100 ΩBarrier20 ΩCopper pair 6.57 ΩTransmitter voltage windowLift-off 12 VTX 21.2 V
VTX = Vsup − 0.022 (RAI + Rbarrier + RCu, round trip)

Calculated results

Allowable load at 22 mA
545.45Ω
Installed load
126.57Ω
Copper round-trip resistance
6.5683Ω
Transmitter terminals at 22 mA
21.215V
Compliance headroom
9.2155V
Load reserve
418.89Ω
NE 43 screening band
Normal
Scaled reading
96EU
HART 250 Ω load
Fail
  • HART uses a 250 Ω minimum DC-load screen. Confirm the modem load window and AC impedance of the complete loop.

Model and interpretation

Full methodology

Screen worst-case load

Both copper conductors count. The nominal copper model uses 0.017241 Ω·mm²/m at 20 °C and a 0.00393/°C temperature coefficient. AWG uses a continuous equivalent area so changing units keeps the same cable. Compare with the cable datasheet and actual minimum supply.

Read NE 43 bands

4–20 mA is the nominal measurement span. This screen uses ≤3.6 mA for low fault and ≥21 mA for high fault. The low guard band is above 3.6 through 3.8 mA. The high guard band is above 20.5 and below 21 mA. Verify the instrument and host configuration. A low current alone cannot distinguish a sensor fault from an open wire or power loss.

Avoid double square rooting

Select square-root scaling for signal current proportional to differential pressure. Leave it linear if the transmitter already outputs linearized flow. Values outside the live range remain mathematical readouts. Verify HART AC load and barrier approvals separately.