ControlLoopLab
Home Digital filtersWorked example

Slow tank level noise bandwidth

A level measurement is smoothed well below PLC scan rate to tame sloshing and electronics noise.

Model inputs

Filter specification
Hz
Hz
Hz

Discrete transfer & step samples

Below Nyquist
Cutoff gain
−3.0103dB
Test phase
−68.682°
Test delay
72.522ms
Noise BW
0.25126Hz
Discrete low-pass attenuation and step responseDiscrete attenuationdB0.01330.07380.4082.2612.5−72−47−223Frequency (Hz, log)Unit-step samplesoutput034.368.5103137−0.080.3070.6931.08Sample index nCutoff markerTest markerStep samples
y[n] = b0 x[n] + b1 x[n−1] + b2 x[n−2] − a1 y[n−1] − a2 y[n−2]

Calculated results

b0
0.03940939324831417
b1
0
b2
0
a1
-0.9605906067516858
a2
0
DC gain
1×
Cutoff attenuation
−3.0103dB
Cutoff phase
−43.86°
Cutoff group delay
11.937samples
Cutoff group delay
477.49ms
Test attenuation
−10.316dB
Test phase
−68.682°
Test group delay
1.813samples
Test group delay
72.522ms
95% first crossing
2960ms
99% first crossing
4560ms
Equivalent noise bandwidth
0.25126Hz

Model and interpretation

Full methodology

Set cutoff in digital frequency

Cutoff is strictly between DC and Nyquist. EMA uses the exact digital half-power coefficient. Tustin and Butterworth prewarp the cutoff before bilinear conversion. The denominator uses a0 = 1 and the negative-feedback convention shown above.

Read phase and delay separately

Phase is ∠H(eʲω). Group delay is −d∠H/dω in samples and can differ sharply from phase delay. At a Nyquist transmission zero the displayed phase is the one-sided limit. The noise bandwidth is the one-sided integral of |H|² at unity DC.

Check how the firmware represents it

Step times show the first sample at or past 95% and 99%, with the input step at n = 0. Near DC or Nyquist, implement a suitable factored or high-precision realization and recheck coefficient quantization.