Tank level loop in the low fault band
A level input is configured for low fault signaling and is measured outside the live range.
Model inputs
- Loop supply
- 24 V
- Transmitter lift-off
- 12 V
- AI receiver
- 250 Ω
- Safety barrier
- 0 Ω
- One-way cable run
- 72 m
- Copper conductor
- 0.5189 mm²
- Cable temperature
- 45 °C
- HART modem
- Check 250 Ω minimum
- Measured current
- 3.55 mA
- Transmitter output
- Linear PV
- Lower range (LRV)
- 0 EU
- Upper range (URV)
- 12 EU
Model inputs
Fractional AWG shows the equivalent copper area.
Two-wire circuit & voltage reserve
Sensor break / low fault- Headroom
- 6.3844V
- Loop load
- 255.25Ω
- Scaled value
- −0.3375EU
- Input current
- 3.55mA
Calculated results
- Allowable load at 22 mA
- 545.45Ω
- Installed load
- 255.25Ω
- Copper round-trip resistance
- 5.2546Ω
- Transmitter terminals at 22 mA
- 18.384V
- Compliance headroom
- 6.3844V
- Load reserve
- 290.2Ω
- NE 43 screening band
- Sensor break / low fault
- Scaled reading
- −0.3375EU
- HART 250 Ω load
- Pass
- The scaled value is mathematical only. Treat an out-of-range or fault-band signal according to the transmitter and host configuration.
- HART uses a 250 Ω minimum DC-load screen. Confirm the modem load window and AC impedance of the complete loop.
Model and interpretation
Full methodologyScreen worst-case load
Both copper conductors count. The nominal copper model uses 0.017241 Ω·mm²/m at 20 °C and a 0.00393/°C temperature coefficient. AWG uses a continuous equivalent area so changing units keeps the same cable. Compare with the cable datasheet and actual minimum supply.
Read NE 43 bands
4–20 mA is the nominal measurement span. This screen uses ≤3.6 mA for low fault and ≥21 mA for high fault. The low guard band is above 3.6 through 3.8 mA. The high guard band is above 20.5 and below 21 mA. Verify the instrument and host configuration. A low current alone cannot distinguish a sensor fault from an open wire or power loss.
Avoid double square rooting
Select square-root scaling for signal current proportional to differential pressure. Leave it linear if the transmitter already outputs linearized flow. Values outside the live range remain mathematical readouts. Verify HART AC load and barrier approvals separately.