4–20 mA & HART loop budget

Size a two-wire loop at 22 mA, screen HART load and decode a linear or square-root process reading.

Model inputs

Supply & wiring
V
V
Ω
Ω
m
mm²
°C
Current scaling
mA
EU
EU

Fractional AWG shows the equivalent copper area.

Two-wire circuit & voltage reserve

In range
Headroom
4.561V
Loop load
338.14Ω
Scaled value
80EU
Input current
12mA
Two-wire circuit and transmitter voltagePowered two-wire loop22 mA checkDC supply24 VTransmitter16.6 VAI load250 ΩBarrier75 ΩCopper pair 13.1 ΩTransmitter voltage windowLift-off 12 VTX 16.6 V
VTX = Vsup − 0.022 (RAI + Rbarrier + RCu, round trip)

Calculated results

Allowable load at 22 mA
545.45Ω
Installed load
338.14Ω
Copper round-trip resistance
13.137Ω
Transmitter terminals at 22 mA
16.561V
Compliance headroom
4.561V
Load reserve
207.32Ω
NE 43 screening band
Normal
Scaled reading
80EU
HART 250 Ω load
Pass
  • HART uses a 250 Ω minimum DC-load screen. Confirm the modem load window and AC impedance of the complete loop.

Model and interpretation

Full methodology

Screen worst-case load

Both copper conductors count. The nominal copper model uses 0.017241 Ω·mm²/m at 20 °C and a 0.00393/°C temperature coefficient. AWG uses a continuous equivalent area so changing units keeps the same cable. Compare with the cable datasheet and actual minimum supply.

Read NE 43 bands

4–20 mA is the nominal measurement span. This screen uses ≤3.6 mA for low fault and ≥21 mA for high fault. The low guard band is above 3.6 through 3.8 mA. The high guard band is above 20.5 and below 21 mA. Verify the instrument and host configuration. A low current alone cannot distinguish a sensor fault from an open wire or power loss.

Avoid double square rooting

Select square-root scaling for signal current proportional to differential pressure. Leave it linear if the transmitter already outputs linearized flow. Values outside the live range remain mathematical readouts. Verify HART AC load and barrier approvals separately.