NFPA 13 · Worked example
About 600 gallons without a quick-opening device
An expanded non-dwelling dry system contains about 600 gallons of internal volume and has no quick-opening device.
Inputs
Supervisory pressure fill curve
Edit inputsAbove the selected allowance. Evaluate the applicable timed delivery test or listed calculation.
How to read this example
The 500-gallon screening path is exceeded. Compare water delivery options separately from the air compressor result.
Open the base calculatorCalculated values
- Total system volume
- 622.21 gal
- Pipe volume subtotal
- 612.21 gal
- Free air added from 0 psig
- 198.09 ft³
- Required free-air delivery
- 7 SCFM
- Modeled fill time
- 23.03 min
- Compressor delivery reserve
- 2 SCFM
- Selected dry-pipe volume allowance
- 500 gal
- Dry-pipe volume reserve
- -122.21 gal
Pipe volume by run 4 rows
| Run | Internal borein | Lengthft | Volumegal |
|---|---|---|---|
| 1 | 4.26 | 570 | 422 |
| 2 | 2.157 | 680 | 129.1 |
| 3 | 1.442 | 720 | 61.1 |
| 4 | 1.097 | 0 | 0 |
Equations and assumptions
V_pipe = Σ π d² L / 4V_free = V_system × P_gauge / P_atmFAD_30 = V_free / 30 + leakage
The non-dwelling dry-pipe volume screening paths are 500 gal without a quick-opening device or 750 gal with one. Larger volumes can use applicable timed delivery or listed calculation paths. Dwelling dry pipe and preaction require their own delivery criteria.
The isothermal fill starts at 0 psig with free air referenced to 14.696 psia. Use delivered compressor airflow at the target pressure and the valve manufacturer’s supervisory setpoint.
The 30-minute curve describes air restoration. Water delivery after sprinkler operation is evaluated separately.