NFPA 291 · Worked example
Rounded outlet field test
A 2½ in. rounded outlet measures 25 psi pitot. At the monitor hydrant, the static and flowing pressures are 74 and 57 psi.
Inputs
Water supply curve
Edit inputsPredicted pressure at demand flow meets the entered pressure at the test datum.
How to read this example
Compare supply at 980 GPM and 47 psi with the 20 psi reference capacity. Those outputs answer different questions about the test.
Open the base calculatorCalculated values
- First group · flow per outlet
- 839.25 GPM
- Second group · flow per outlet
- 0 GPM
- Total measured flow
- 839.25 GPM
- Measured residual drop
- 17 psi
- Measured pressure drop
- 23 %
- Reference flow at 20 psi / 1.38 bar
- 1,566.54 GPM
- Supply pressure at demand flow
- 51.35 psi
- Pressure margin at demand flow
- 4.35 psi
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.