NFPA 291 · Worked example
Demand above a weak supply curve
At high demand, a supply with 48 psi static and 29 psi flowing residual cannot sustain an 800 GPM, 35 psi system duty.
Inputs
Water supply curve
Edit inputsPredicted supply pressure at the specified demand flow is below the required pressure.
How to read this example
Read the demand marker above the curve and carry the pressure deficit into a separate supply or booster evaluation.
Open the base calculatorCalculated values
- First group · flow per outlet
- 628.04 GPM
- Second group · flow per outlet
- 0 GPM
- Total measured flow
- 628.04 GPM
- Measured residual drop
- 19 psi
- Measured pressure drop
- 39.6 %
- Reference flow at 20 psi / 1.38 bar
- 774.33 GPM
- Supply pressure at demand flow
- 18.27 psi
- Pressure margin at demand flow
- -16.73 psi
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.