NFPA 291 · Worked example
Strong main with a small test drop
The test flows one outlet while the monitor pressure falls only four psi from its 82 psi starting point.
Inputs
Water supply curve
Edit inputsThe test produced less than a 10% pressure drop. Extrapolated flow is sensitive to gauge error.
How to read this example
The predicted 20 psi flow is sensitive to the small denominator. Repeat the field test with a suitable flow and verify gauge resolution.
Open the base calculatorCalculated values
- First group · flow per outlet
- 855.87 GPM
- Second group · flow per outlet
- 0 GPM
- Total measured flow
- 855.87 GPM
- Measured residual drop
- 4 psi
- Measured pressure drop
- 4.9 %
- Reference flow at 20 psi / 1.38 bar
- 3,759.99 GPM
- Supply pressure at demand flow
- 75.64 psi
- Pressure margin at demand flow
- 27.64 psi
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.