NFPA 291 · Worked example

Square outlet with lower residual pressure

A square-edged 2½ in. outlet has a 20 psi pitot reading. The monitor hydrant drops from 64 to 40 psi.

Inputs

Flowing outlets
in
psi
Pressure hydrant and demand
psi
psi

Read static and flowing residual at the same monitor hydrant.

GPM
psi

Use the test gauge elevation datum.

Water supply curve

Worksheet units
Edit inputs
Water supply curve · Input-linked engineering diagramTEST FLOW667.24GPM20 PSI FLOW925.62GPMSUPPLY HEAD36.37psiHEAD RESERVE-6.63psiPressure · psiSupply curveDemand point05010001,0002,000Flow · GPMSupply vs. demand pressure-6.63 psi0 psi43 psi target86 psi
Demand point above supply

Predicted supply pressure at the specified demand flow is below the required pressure.

How to read this example

The 0.80 discharge coefficient changes the measured flow used to anchor the extrapolation. Use the actual outlet profile.

Open the base calculator

Calculated values

First group · flow per outlet
667.24 GPM
Second group · flow per outlet
0 GPM
Total measured flow
667.24 GPM
Measured residual drop
24 psi
Measured pressure drop
37.5 %
Reference flow at 20 psi / 1.38 bar
925.62 GPM
Supply pressure at demand flow
36.37 psi
Pressure margin at demand flow
-6.63 psi

Equations and assumptions

  • Q_outlet = 29.84 c d² √P_pitot
  • Q_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴
  • P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵

The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.

Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.

Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.

Source references