NFPA 291 · Worked example

Rounded outlet field test

A 2½ in. rounded outlet measures 25 psi pitot. At the monitor hydrant, the static and flowing pressures are 74 and 57 psi.

Inputs

Flowing outlets
in
psi
Pressure hydrant and demand
psi
psi

Read static and flowing residual at the same monitor hydrant.

GPM
psi

Use the test gauge elevation datum.

Water supply curve

Worksheet units
Edit inputs
Water supply curve · Input-linked engineering diagramTEST FLOW839.25GPM20 PSI FLOW1,566.54GPMSUPPLY HEAD51.35psiHEAD RESERVE4.35psiPressure · psiSupply curveDemand point05010001,0002,000Flow · GPMSupply vs. demand pressure+4.35 psi0 psi47 psi target94 psi
Demand point below supply

Predicted pressure at demand flow meets the entered pressure at the test datum.

How to read this example

Compare supply at 980 GPM and 47 psi with the 20 psi reference capacity. Those outputs answer different questions about the test.

Open the base calculator

Calculated values

First group · flow per outlet
839.25 GPM
Second group · flow per outlet
0 GPM
Total measured flow
839.25 GPM
Measured residual drop
17 psi
Measured pressure drop
23 %
Reference flow at 20 psi / 1.38 bar
1,566.54 GPM
Supply pressure at demand flow
51.35 psi
Pressure margin at demand flow
4.35 psi

Equations and assumptions

  • Q_outlet = 29.84 c d² √P_pitot
  • Q_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴
  • P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵

The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.

Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.

Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.