NFPA 291 · Worked example

Strong main with a small test drop

The test flows one outlet while the monitor pressure falls only four psi from its 82 psi starting point.

Inputs

Flowing outlets
in
psi
Pressure hydrant and demand
psi
psi

Read static and flowing residual at the same monitor hydrant.

GPM
psi

Use the test gauge elevation datum.

Water supply curve

Worksheet units
Edit inputs
Water supply curve · Input-linked engineering diagramTEST FLOW855.87GPM20 PSI FLOW3,759.99GPMSUPPLY HEAD75.64psiHEAD RESERVE27.64psiPressure · psiSupply curveDemand point05010002,5005,000Flow · GPMSupply vs. demand pressure+27.64 psi0 psi48 psi target96 psi
Review the flow test

The test produced less than a 10% pressure drop. Extrapolated flow is sensitive to gauge error.

How to read this example

The predicted 20 psi flow is sensitive to the small denominator. Repeat the field test with a suitable flow and verify gauge resolution.

Open the base calculator

Calculated values

First group · flow per outlet
855.87 GPM
Second group · flow per outlet
0 GPM
Total measured flow
855.87 GPM
Measured residual drop
4 psi
Measured pressure drop
4.9 %
Reference flow at 20 psi / 1.38 bar
3,759.99 GPM
Supply pressure at demand flow
75.64 psi
Pressure margin at demand flow
27.64 psi

Equations and assumptions

  • Q_outlet = 29.84 c d² √P_pitot
  • Q_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴
  • P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵

The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.

Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.

Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.