NFPA 13 · Worked example

Extra Hazard Group 2 remote head

A preliminary 0.40 GPM/ft² point is applied to a 100 ft² footprint with an 11.2 K-factor and 13 psi residual.

Inputs

Sprinkler head
GPM/√psi

Enter the listed K-factor in the selected units.

psi
psi

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
ft²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE40.38GPMDENSITY FLOW40GPMMIN. PRESSURE12.76psiFLOW RESERVE0.38GPMBRANCH LINEK 11.2 GPM/√psiDensity 0.4 GPM/ft²100 ft² coverageDischarge vs. required flow+0.38 GPM0 GPM40 GPM target80 GPM
Flow and pressure targets met

Discharge and end-head pressure both meet the entered targets.

How to read this example

Compare the small flow reserve with the separate operating pressure floor. Check the applicable listing and design area before assigning a real footprint.

Open the base calculator

Calculated values

Delivered flow
40.38 GPM
Required density flow
40 GPM
Flow reserve
0.38 GPM
Required head pressure
12.76 psi
Minimum pressure floor
7 psi
Reserve above pressure floor
6 psi
Pressure for density alone
12.76 psi
Design density
0.4 GPM/ft²
Hydraulic coverage at entered density
100.96 ft²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.