NFPA 13 · Worked example
Extra Hazard Group 2 remote head
A preliminary 0.40 GPM/ft² point is applied to a 100 ft² footprint with an 11.2 K-factor and 13 psi residual.
Inputs
Remote sprinkler section
Edit inputsDischarge and end-head pressure both meet the entered targets.
How to read this example
Compare the small flow reserve with the separate operating pressure floor. Check the applicable listing and design area before assigning a real footprint.
Open the base calculatorCalculated values
- Delivered flow
- 40.38 GPM
- Required density flow
- 40 GPM
- Flow reserve
- 0.38 GPM
- Required head pressure
- 12.76 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- 6 psi
- Pressure for density alone
- 12.76 psi
- Design density
- 0.4 GPM/ft²
- Hydraulic coverage at entered density
- 100.96 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.